2.2 A: Initialization Parameters
No.
Name
(Hex.)
A1-06
Application Preset
(0127)
The drive software contains the application presets shown below. Set A1-06 to align with the application to let the
drive automatically set the best parameter settings for the selected application. The drive saves parameters frequently
used for the application in parameters A2-01 to A2-16 [User Parameters 1 to 16] for easy configuration and reference
in [User Custom Parameters] in the main menu.
• General purpose fan
• Fan with PID Control function
• Return fan
• Cooling tower fan
• Secondary pump
• Pump with PID control function
• Pump network multiplex
Note:
• Before you set A1-06, make sure that you set A1-03 = 2220, 3330 [Initialize Parameters = 2-Wire Initialization, 3-Wire Initialization] to
initialize parameters.
• It is not possible to change the A1-06 value. To set an application preset, first set A1-03 = 2220 to initialize parameters, then set this
parameter. If initializing all parameters will cause a problem, do not change the settings.
If you set A2-33 = 1 [User Parameter Auto Selection = Enabled: Auto Save Recent Parms] to set parameters to A2-17 to A2-32 [User
Parameters 17 to 32] automatically, the drive will reset these parameters when you change the A1-06 setting.
0 : No Preset Selected
The drive saves the parameters in
Table 2.3 Parameters Saved as User Parameters with the No Preset Selected
User Parameter No.
A2-01
A2-02
A2-03
A2-04
A2-05
A2-06
A2-07
A2-08
A2-09
A2-10
A2-11
A2-12
A2-13
A2-14
A2-15
A2-16
A2-17
A2-18
A2-19
A2-20
A2-21
A2-22
166
V/f
OLV/PM EZOLV
OLV/PM
Sets the drive to operate in selected application conditions.
Table 2.3
as user parameters.
Parameter No. Saved
A1-02
b1-01
b1-02
b1-03
C1-01
C1-02
C6-02
d1-01
d1-02
d1-03
d1-04
d1-17
E1-01
E1-03
E1-04
E1-05
E1-06
E1-09
E1-13
E2-01
E2-04
E2-11
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Default
(Range)
0
(0 - 8)
Name
Control Method Selection
Frequency Reference Selection 1
Run Command Selection 1
Stopping Method Selection
Acceleration Time 1
Deceleration Time 1
Carrier Frequency Selection
Reference 1
Reference 2
Reference 3
Reference 4
Jog Reference
Input AC Supply Voltage
V/f Pattern Selection
Maximum Output Frequency
Maximum Output Voltage
Base Frequency
Minimum Output Frequency
Base Voltage
Motor Rated Current (FLA)
Motor Pole Count
Motor Rated Power