YASKAWA HV600 Manual page 438

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

2.12 S: Special Applications
S2-11: Timer 3 Start Time
No.
Name
(Hex.)
S2-11
Timer 3 Start Time
(3210)
Note:
• Default is when o4-22 = 1 [Time Format = 12 Hour Clock]. When o4-22 = 0 [24 Hour Clock], default is 00:00. When o4-22 = 2 [12 Hour
JP Clock], default is 00:00 AM.
• Range is when o4-22 = 1. When o4-22 = 0, range is 00:00 to 24:00. When o4-22 = 2, range is 00:00 AM to 11:59 PM.
S2-12: Timer 3 Stop Time
No.
Name
(Hex.)
S2-12
Timer 3 Stop Time
(3211)
Note:
• Default is when o4-22 = 1 [Time Format = 12 Hour Clock]. When o4-22 = 0 [24 Hour Clock], default is 00:00. When o4-22 = 2 [12 Hour
JP Clock], default is 00:00 AM.
• Range is when o4-22 = 1. When o4-22 = 0, range is 00:00 to 24:00. When o4-22 = 2, range is 00:00 AM to 11:59 PM.
S2-13: Timer 3 Day Selection
No.
Name
(Hex.)
S2-13
Timer 3 Day Selection
(3212)
0 : Timer Disabled
1 : Daily
2 : Mon - Fri
3 : Sat - Sun
4 : Monday
5 : Tuesday
6 : Wednesday
7 : Thursday
8 : Friday
9 : Saturday
10 : Sunday
S2-14: Timer 3 Sequence Selection
No.
Name
(Hex.)
S2-14
Timer 3 Sequence Selection
(3213)
0 : Digital Out Only
1 : Run
2 : Run - PID Disable
3 : Allow Alternation
438
V/f
OLV/PM EZOLV
OLV/PM
Sets the start time for timer 3.
V/f
OLV/PM EZOLV
OLV/PM
Sets the stop time for timer 3.
V/f
OLV/PM EZOLV
OLV/PM
Sets the days for which sequence timer 3 is active.
V/f
OLV/PM EZOLV
OLV/PM
Sets the drive response when sequence timer 3 is active.
Description
Description
Description
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Default
(Range)
12:00
(12:00 AM - 11:59 PM)
Default
(Range)
12:00
(12:00 AM - 11:59 PM)
Default
(Range)
0
(0 - 10)
Default
(Range)
0
(0 - 3)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents