YASKAWA HV600 Manual page 31

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

No.
Name
(Hex.)
b5-08
PID Primary Delay Time
Constant
(01AC)
RUN
Expert
b5-09
PID Output Level
Selection
(01AD)
b5-10
PID Output Gain Setting
(01AE)
RUN
b5-11
PID Output Reverse
Selection
(01AF)
b5-17
PID Accel/Decel Time
(01B5)
RUN
b5-28
PID Feedback Square
Root Sel
(01EA)
b5-29
PID Feedback Square
Root Gain
(01EB)
b5-30
PID Feedback Offset
(01EC)
b5-34
PID Output Lower Limit
Level
(019F)
RUN
b5-35
PID Input Limit Level
(01A0)
RUN
b5-38
PID User Unit Display
Scaling
(01FE)
b5-39
PID User Unit Display
Digits
(01FF)
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Description
V/f
OLV/PM
OLV/PM EZOLV
Sets the primary delay time constant for the PID control output. Usually it is not necessary
to change this setting.
V/f
OLV/PM EZOLV
OLV/PM
Sets the polarity of the PID output.
0 : Normal Output (Direct Acting)
1 : Reverse Output (Reverse Acting)
V/f
OLV/PM EZOLV
OLV/PM
Sets the amount of gain to apply to the PID output.
V/f
OLV/PM EZOLV
OLV/PM
Sets the function that enables and disables reverse motor rotation for negative PID control
output.
0 : Lower Limit is Zero
1 : Negative Output Accepted
V/f
OLV/PM EZOLV
OLV/PM
Raises or lowers the PID setpoint using the acceleration and deceleration times set to the
drive. This is a soft-starter for the PID setpoint.
V/f
OLV/PM
OLV/PM EZOLV
Enables and disables the square root of the PID Feedback compared to the PID Setpoint to
set an appropriate drive output for the correct system regulation.
0 : Disabled
1 : Enabled
V/f
OLV/PM
OLV/PM EZOLV
Sets the multiplier applied to the square root of the feedback.
V/f
OLV/PM
OLV/PM EZOLV
Sets PID feedback Offset as a percentage of maximum frequency.
V/f
OLV/PM EZOLV
OLV/PM
Sets the output lower limit for the PID control as a percentage of the Maximum Output
Frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum
output frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
V/f
OLV/PM
OLV/PM EZOLV
Sets the output upper limit for the PID control as a percentage of the Maximum Output
Frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum
output frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
V/f
OLV/PM
OLV/PM EZOLV
Sets the value that the drive sets or shows as the PID setpoint when at the maximum output
frequency.
V/f
OLV/PM
OLV/PM EZOLV
Sets the number of digits to set and show the PID setpoint.
0 : No Decimal Places (XXXXX)
1 : One Decimal Places (XXXX.X)
2 : Two Decimal Places (XXX.XX)
3 : Three Decimal Places (XX.XXX)
1.5 b: Application
Default
Ref.
(Range)
0.00 s
209
(0.00 - 10.00 s)
0
209
(0, 1)
1.00
210
(0.00 - 25.00)
0
210
(0, 1)
0.0 s
210
(0.0 - 6000.0 s)
0
210
(0, 1)
0.00
210
(0.00 - 2.00)
0.00%
211
(0.00 - 100.00%)
0.0%
211
(-100.0 - +100.0%)
1000.0%
211
(0.0 - 1000.0%)
100.00
211
(0.01 - 600.00)
2
211
(0 - 3)
31
1