2.13 T: Auto-Tuning
T1-11: Motor Iron Loss
No.
Name
(Hex.)
T1-11
Motor Iron Loss
(070B)
Note:
The default setting is different for different motor codes and motor parameter settings.
The value shown is the E2-10 [Motor Iron Loss] or E4-10 [Motor 2 Iron Loss] for the motor output set in T1-02
[Motor Rated Power]. If the motor test report is available, enter the motor iron loss value to T1-11.

T2: PM Motor Auto-Tuning

T2 parameters set the Auto-Tuning input data for PM motor tuning.
Note:
The drive automatically sets these PM motor parameters:
• E1-xx [V/f Pattern for Motor 1]
• E5-xx [V/f Pattern for Motor 1]
T2-01: PM Auto-Tuning Selection
No.
Name
(Hex.)
T2-01
PM Auto-Tuning Selection
(0750)
Note:
Yaskawa recommends Rotational (Ld, Lq, R, back-EMF) for specialized motors. Rotational Auto-Tuning rotates the motor to measure the
actual induction voltage constants for more accurate control than Stationary Auto-Tuning.
0 : Manual Entry w/ Motor Data Sheet
1 : Stationary (Ld, Lq, R)
2 : Stationary (R Only)
4 : Rotational (Ld, Lq, R, back-EMF)
5 : High Frequency Injection
T2-02: PM Motor Code Selection
No.
Name
(Hex.)
T2-02
PM Motor Code Selection
(0751)
Enter the motor code in this parameter to automatically set parameters T2-03 to T2-14. When you are operating a
specialized motor or a non-Yaskawa motor, set this parameter to FFFF and enter the data from the motor nameplate
or the motor test report.
You can only enter the permitted PM motor codes. Different drive control methods will accept different PM motor
codes.
T2-03: PM Motor Type
No.
Name
(Hex.)
T2-03
PM Motor Type
(0752)
0 : IPM motor
IPM motors have magnets in the rotor, and Ld ≠ Lq.
462
V/f
OLV/PM EZOLV
OLV/PM
Sets the iron loss for calculating the energy-saving coefficient.
V/f
OLV/PM EZOLV
OLV/PM
Sets the type of Auto-Tuning for PM motors.
V/f
OLV/PM EZOLV
OLV/PM
Enter the PM motor code as specified by the rotation speed and motor output.
V/f
OLV/PM EZOLV
OLV/PM
Sets the type of PM motor the drive will operate.
Description
Description
Description
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Default
(Range)
Determined by E2-11 or E4-
11
(0 - 65535 W)
Default
(Range)
0
(0 - 5)
Default
(Range)
FFFF
(0000 - FFFF)
Default
(Range)
1
(0, 1)