YASKAWA HV600 Manual page 371

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

L5-04:
Figure 2.94 Time Chart for Early Cancellation of Auto-Restart Function
1 : Always Active
The drive always activates fault output.
L5-04: Interval Method Restart Time
No.
Name
(Hex.)
L5-04
Interval Method Restart
Time
(046C)
L5-07: Fault Reset Enable Select Grp1
No.
Name
(Hex.)
L5-07
Fault Reset Enable Select
Grp1
(0B2A)
0000 : Disabled
0001 : Enabled (—/—/—/oL4)
0010 : Enabled (—/—/oL3/—)
0011 : Enabled (—/—/oL3/oL4)
0100 : Enabled (—/oL2/—/—)
0101 : Enabled (—/oL2/—/oL4)
0110 : Enabled (—/oL2/oL3/—)
0111 : Enabled (—/oL2/oL3/oL4)
1000 : Enabled (oL1/—/—/—)
1001 : Enabled (oL1/—/—/oL4)
1010 : Enabled (oL1/—/oL3/—)
1011 : Enabled (oL1/—/oL3/oL4)
1100 : Enabled (oL1/oL2/—/—)
1101 : Enabled (oL1/oL2/—/oL4)
1110 : Enabled (oL1/oL2/oL3/—)
1111 : Enabled (oL1/oL2/oL3/oL4)
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM EZOLV
OLV/PM
Sets the time interval between each Auto Restart attempt.
V/f
OLV/PM EZOLV
OLV/PM
Use these 4 digits to set the Auto Restart function for oL1 to oL4. From left to right, the digits set
oL1, oL2, oL3, and oL4, in order.
U1-02:
Description
Description
2.9 L: Protection Functions
Default
(Range)
10.0 s
(0.5 - 3600.0 s)
Default
(Range)
1111
(0000 - 1111)
2
371

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents