Mfdi Setting Value - YASKAWA HV600 Manual

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

2.8 H: Terminal Functions
H1-72: Terminal S2 Off-Delay Time
No.
Name
(Hex.)
H1-72
Terminal S2 Off-Delay Time
(39EC)
RUN
H1-73: Terminal S3 Off-Delay Time
No.
Name
(Hex.)
H1-73
Terminal S3 Off-Delay Time
(39ED)
RUN
H1-74: Terminal S4 Off-Delay Time
No.
Name
(Hex.)
H1-74
Terminal S4 Off-Delay Time
(39EE)
RUN
H1-75: Terminal S5 Off-Delay Time
No.
Name
(Hex.)
H1-75
Terminal S5 Off-Delay Time
(39EF)
RUN
H1-76: Terminal S6 Off-Delay Time
No.
Name
(Hex.)
H1-76
Terminal S6 Off-Delay Time
(39F0)
RUN
H1-77: Terminal S7 Off-Delay Time
No.
Name
(Hex.)
H1-77
Terminal S7 Off-Delay Time
(39F1)
RUN

MFDI Setting Value

Selects a function set with H1-01 to H1-07.
0: 3-Wire Sequence
Setting Value
Function
0
3-Wire Sequence
If the 3-wire sequence is set to a terminal that is not MFDI terminals S1 and S2, these terminals will be the input
terminals for Forward run/Reverse run command. The drive will automatically set terminal S1 to Run command
(RUN) and terminal S2 to Stop command (STOP).
282
V/f
OLV/PM
OLV/PM EZOLV
Sets the length of time necessary for Terminal S2 to be open before the drive removes the
programmed function.
V/f
OLV/PM
OLV/PM EZOLV
Sets the length of time necessary for Terminal S3 to be open before the drive removes the
programmed function.
V/f
OLV/PM EZOLV
OLV/PM
Sets the length of time necessary for Terminal S4 to be open before the drive removes the
programmed function.
V/f
OLV/PM
OLV/PM EZOLV
Sets the length of time necessary for Terminal S5 to be open before the drive removes the
programmed function.
V/f
OLV/PM
OLV/PM EZOLV
Sets the length of time necessary for Terminal S6 to be open before the drive removes the
programmed function.
V/f
OLV/PM EZOLV
OLV/PM
Sets the length of time necessary for Terminal S7 to be open before the drive removes the
programmed function.
V/f
OLV/PM EZOLV
OLV/PM
Sets the direction of motor rotation for 3-wire sequence.
Description
Description
Description
Description
Description
Description
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Default
(Range)
0.00 s
(0.00 - 300.00 s)
Default
(Range)
0.00 s
(0.00 - 300.00 s)
Default
(Range)
0.00 s
(0.00 - 300.00 s)
Default
(Range)
0.00 s
(0.00 - 300.00 s)
Default
(Range)
0.00 s
(0.00 - 300.00 s)
Default
(Range)
0.00 s
(0.00 - 300.00 s)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents