2.14 Y: Application Features
Note:
• The unit, decimal place, and setting range change when the Y1-07 [Minimum Speed Units] setting changes:
–Y1-07 = 0 [Hz]: The setting range is 0.0 Hz to E1-04 Hz.
–Y1-07 = 1 [RPM]: The setting range is 0 RPM to (E1-04 × 60) RPM.
• When A1-02 = 8 [Control Method Selection = EZ Vector Control], the range is 0.0 Hz to (E9-02 × 2) Hz.
Y1-07: Minimum Speed Units
No.
Name
(Hex.)
Y1-07
Minimum Speed Units
(3C06)
0 : Hz
1 : RPM
Note:
Changing Y1-07 will set Y1-06 [Minimum Speed] to the default value.
Y1-08: Low Feedback Level
No.
Name
(Hex.)
Y1-08
Low Feedback Level
(3C07)
RUN
Note:
• Unit and decimal place change when the system units change.
• Range is 0.00 to 99.99 with sign-bit "-" indicating Delta to Setpoint.
Y1-09: Low Feedback Lvl Fault Dly Time
No.
Name
(Hex.)
Y1-09
Low Feedback Lvl Fault Dly
Time
(3C08)
RUN
Note:
• Set Y1-10 = 0 [Low Feedback Selection = Fault (and Digital Output)] to enable this parameter.
• When Y1-01 = 3 [Multiplex Mode = Memobus Network], Y9-18 [Staging Mode] uses this value to calculate the quick de-stage feedback
level.
Y1-10: Low Feedback Selection
No.
Name
(Hex.)
Y1-10
Low Feedback Selection
(3C09)
The drive enables the Low Feedback detection when:
• Parameter Y1-08 > 0.0
• Drive is running in AUTO Mode, including sleep boost and feedback drop detection (b5-09 = 0 [PID Output Level
Selection = Normal Output (Direct Acting)])
• There is a Run command, including sleep and timer operation (b5-09 = 1 [Reverse Output (Reverse Acting)])
0 : Fault (and Digital Output)
The keypad will show LFB [Low Feedback Sensed] and the motor coasts to stop. The output terminal set for H2-xx =
97 [MFDO Function Selection = Low Feedback] will activate.
To deactivate the digital output, do a Fault Reset.
1 : Alarm (and Digital Output)
468
V/f
OLV/PM EZOLV
OLV/PM
Sets the units and decimal place for Y1-06 [Minimum Speed].
V/f
OLV/PM
OLV/PM EZOLV
Sets the lower detection level for the PID feedback.
V/f
OLV/PM
OLV/PM EZOLV
Sets the delay time for the drive to detect an LFB [Low Feedback Sensed] fault after the feedback
level decreases to less than the value set in Y1-08 [Low Feedback Level].
V/f
OLV/PM EZOLV
OLV/PM
Sets the drive response when the feedback decreases to less than Y1-08 [Low Feedback Level] for
longer than the time set in Y1-09 [Low Feedback Lvl Fault Dly Time].
Description
Description
Description
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Default
(Range)
0
(0, 1)
Default
(Range)
0.00%
(0.00 - 99.99%)
Default
(Range)
10 s
(0 - 3600 s)
Default
(Range)
0
(0 - 2)