2.8 H: Terminal Functions
11: Reverse Torque Limit
Setting Value
Function
11
Reverse Torque Limit
Note:
When you use L7-01 to L7-04 and analog inputs to set torque limits for the same quadrant, it will enable the lower torque limit.
12: Regenerative Torque Limit
Setting Value
Function
12
Regenerative Torque Limit
Note:
When you use L7-01 to L7-04 and analog inputs to set torque limits for the same quadrant, it will enable the lower torque limit.
15: General Torque Limit
Setting Value
Function
15
General Torque Limit
16: Differential PID Feedback
Setting Value
Function
16
Differential PID Feedback
The drive uses the deviation between the PID feedback and the differential feedback value signals to calculate the PID
input.
1F: Not Used
Setting Value
Function
1F
Not Used
334
Figure 2.77 Torque Limits from Parameters and Analog Inputs
V/f
OLV/PM
OLV/PM EZOLV
Enters the load torque limit if the motor rated torque is 100%.
V/f
OLV/PM
OLV/PM EZOLV
Enters the regenerative torque limit if the motor rated torque is 100%.
V/f
OLV/PM EZOLV
OLV/PM
Enters the torque limit that is the same for all quadrants for forward, reverse, and regenerative operation if the motor rated torque is
100%.
V/f
OLV/PM EZOLV
OLV/PM
Enters the PID differential feedback value if the full scale analog signal (10 V or 20 mA) is 100%.
V/f
OLV/PM
OLV/PM EZOLV
Use this setting for unused terminals or to use terminals in through mode.
Description
Description
Description
Description
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming