YASKAWA HV600 Manual page 447

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

H1-xx = 6D
[AUTO Command]
ON
ON
When S5-04 = 0, you can only use MFDIs set for H1-xx = 6D and 6E individually.
H1-xx = 6D
[AUTO Command]
OFF
ON
-
-
AUTO Command
To input an AUTO command from
• H1-xx = 6D [AUTO Command]
• H1-xx = 6E [HAND Command] when S5-04 = 0 [HAND-OFF-AUTO Behavior = Legacy]
When S5-04 = 0, the drive will receive the AUTO Command when the MFDI set for H1-xx = 6D is activated or when
the MFDI set for H1-xx = 6E is deactivated.
Note:
• If you set the terminal for H1-xx = 6D and 6E at the same time when S5-04 = 0, the drive will detect an oPE34 [HAND/OFF/AUTO Input
Setting].
• When S5-04 = 1 [Normal], the drive will receive the AUTO Command only when the terminal set for H1-xx = 6D is activated and the
terminal set for H1-xx = 6E is deactivated.
In Legacy and Normal modes, the drive establishes the AUTO Run command when the AUTO Command and
External Run command are active.
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
H1-xx = 6E
Operation Mode
[HAND Command]
OFF
ON
Figure 2.115 Drive Operation in Legacy Mode
Table 2.75 MFDI Settings and Drive Operation in Legacy Mode
H1-xx = 6E
Operation Mode
[HAND Command]
-
-
OFF
ON
, you must set these MFDIs:
Frequency Reference Source
AUTO
Based on b1-01
OFF
Based on b1-01
Frequency Reference Source
HAND
Based on S5-01
AUTO
Based on b1-01
AUTO
Based on b1-01
HAND
Based on S5-01
2.12 S: Special Applications
Run Command Source
Based on b1-02
-
Run Command Source
Keypad
Based on b1-02
Based on b1-02
Keypad