B2: Dc Injection Braking And Short Circuit Braking - YASKAWA HV600 Manual

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

Note:
Set this parameter to 0.0 s to disable this function.
When b1-40 > 0.0 s, the drive will coast-to-stop when you remove the Run command and decelerate for the time set
in b1-40. Refer to
Figure 2.15
b1-40:
C1-02:

b2: DC Injection Braking and Short Circuit Braking

b2 parameters set the DC Injection Braking and Short Circuit Braking functions.
• DC Injection Braking: A braking method that injects DC current into the motor windings. This function should not
be used too frequently, because it generates a fair amount of heat in the motor.
• Short Circuit Braking: A braking method for PM motors.
b2-01: DC Injection/Zero SpeedThreshold
No.
Name
(Hex.)
b2-01
DC Injection/Zero
SpeedThreshold
(0189)
Note:
This parameter is available when b1-03 = 0 [Stopping Method Selection = Ramp to Stop].
When the control method selected in A1-02 [Control Method Selection] changes, the b2-01 function changes.
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
for the timing chart.
Figure 2.15 Deceleration Abort Time Chart
V/f
OLV/PM EZOLV
OLV/PM
Sets the frequency to start DC Injection Braking and Short Circuit Braking.
C1-04:
L3-04:
Description
2.3 b: Application
Default
(Range)
Determined by A1-02
(0.0 - 10.0 Hz)
2