S: Special Applications; S1: Dynamic Noise Control; S2: Sequence Run Timers - YASKAWA HV600 Manual

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

1.16 S: Special Applications

1.16

S: Special Applications

S1: Dynamic Noise Control

No.
Name
(Hex.)
S1-01
Dynamic Noise Control
(3200)
S1-02
Voltage Reduction Rate
(3201)
S1-03
Voltage Restoration Level
(3202)
S1-04
Voltage Restoration Off
Level
(3203)
S1-05
Volt Restore Sensitivity
Time K
(3204)
S1-06
Volt Restore Impact Load
Time K
(3205)
S1-07
Output Phase Loss Level
(324C)

S2: Sequence Run Timers

No.
Name
(Hex.)
S2-01
Timer 1 Start Time
(3206)
S2-02
Timer 1 Stop Time
(3207)
S2-03
Timer 1 Day Selection
(3208)
100
V/f
OLV/PM
OLV/PM EZOLV
Sets the function that decreases the output voltage in variable torque applications to
decrease audible noise.
0 : Disabled
1 : Enabled
V/f
OLV/PM EZOLV
OLV/PM
Sets the rate at which the drive will decrease the output voltage as a percentage of the V/f
pattern when operating with no load.
V/f
OLV/PM
OLV/PM EZOLV
Sets the level at which the drive will start to restore the voltage as a percentage of the drive
rated torque.
V/f
OLV/PM EZOLV
OLV/PM
Sets the level at which voltage restoration for the V/f pattern is complete as a percentage of
the drive rated torque. If the output is more than S1-04, the drive will control the voltage as
specified by the V/f pattern setting.
Note:
The lower limit of this parameter is the value of S1-03 [Voltage Restoration Level] +
10.0%.
V/f
OLV/PM EZOLV
OLV/PM
Sets the level of sensitivity of the output torque and LPF time constant for the voltage
reduction rate. You can adjust the level of sensitivity with the load response.
V/f
OLV/PM EZOLV
OLV/PM
Sets the voltage restoration time constant when you add an impact load.
V/f
OLV/PM EZOLV
OLV/PM
Decreases the output phase loss level when Dynamic Noise control is active.
V/f
OLV/PM
OLV/PM EZOLV
Sets the start time for timer 1.
Note:
• Default is when o4-22 = 1 [Time Format = 12 Hour Clock]. When o4-22 = 0 [24
Hour Clock], default is 00:00. When o4-22 = 2 [12 Hour JP Clock], default is 00:00
AM.
• Range is when o4-22 = 1. When o4-22 = 0, range is 00:00 to 24:00. When o4-22 =
2, range is 00:00 AM to 11:59 PM.
V/f
OLV/PM EZOLV
OLV/PM
Sets the stop time for timer 1.
Note:
• Default is when o4-22 = 1 [Time Format = 12 Hour Clock]. When o4-22 = 0 [24
Hour Clock], default is 00:00. When o4-22 = 2 [12 Hour JP Clock], default is 00:00
AM.
• Range is when o4-22 = 1. When o4-22 = 0, range is 00:00 to 24:00. When o4-22 =
2, range is 00:00 AM to 11:59 PM.
V/f
OLV/PM EZOLV
OLV/PM
Sets the days for which sequence timer 1 is active.
0 : Timer Disabled
1 : Daily
2 : Mon - Fri
3 : Sat - Sun
4 : Monday
5 : Tuesday
6 : Wednesday
7 : Thursday
8 : Friday
9 : Saturday
10 : Sunday
Description
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Default
Ref.
(Range)
1
430
(0, 1)
50.0%
431
(50.0 - 100.0%)
20.0%
431
(0.0 - 90.0%)
50.0%
431
(10.0 - 100.0%)
1.000 s
431
(0.000 - 3.000 s)
0.050 s
431
(0.000 - 1.000 s)
100.0%
431
(10.0 - 100.0%)
Default
Ref.
(Range)
12:00
435
(12:00 AM - 11:59 PM)
12:00
435
(12:00 AM - 11:59 PM)
0
435
(0 - 10)