2.9 L: Protection Functions
Note:
You can disable Auto Restart for faults if you must not restart the machine after the fault.
Fault
Name
CE
Modbus Communication Error
WIRE Break
FDBKL
GF
Ground Fault
High Feedback Sensed
HFB
Output Phase Loss
LF
Low Feedback Sensed
LFB
Loss of Prime
LOP
NMS
Setpoint Not Met
Overcurrent
oC
Heatsink Overheat
oH1
*1
Uv1 is the target for the auto restart process when L2-01 = 1 or 2 [Power Loss Ride Through Select = Enabled for L2-02 Time or Enabled
while CPU Power Active].
Note:
• The Fault Restart method is limited to the interval time that the drive will use L5-04 [Interval Method Restart Time].
• When L5-49 = 1 [Fault Retry Speed Search Select = Enabled], the drive will do a speed search when it resets and restarts after a fault.
• The drive will force the output frequency to zero during the auto-restart interval time.
• If you remove the Run (or HAND) command during the auto-restart interval time, the drive will immediately detect a fault and reset the
fault.
• The LOP [Loss of Prime] fault uses Y1-23 [Prime Loss Max Restart Time] for Auto Restart time. The other faults use L5-04 for Auto
Restart time.
• When you enable Thrust or Pre-Charge Modes, the drive will operate them correctly
L5-01: Number of Auto-Restart Attempts
No.
Name
(Hex.)
L5-01
Number of Auto-Restart
Attempts
(049E)
The drive resets the number of Auto Restart attempts to 0 in these conditions:
• The drive operates correctly for 10 minutes after a fault restart.
• When you manually clear a fault after the drive triggers protective functions.
• When you re-energize the drive.
L5-02: Fault Contact at Restart Select
No.
Name
(Hex.)
L5-02
Fault Contact at Restart
Select
(049F)
0 : Active Only when Not Restarting
The drive will only activate fault output when the drive cancels the Auto Restart function.
When you remove the Run command during the time set in L5-04 [Interval Method Restart Time], the drive will
cancel the Auto Restart function. At the same time, the drive will activate the fault output. Refer to
more information.
370
Table 2.60 List of Faults during which Auto Restart is Available
Parameters to Disable Auto
Restart
H5-36
L5-42
L5-08
L5-41
-
L5-40
L5-51
L5-50
-
L5-08
V/f
OLV/PM
OLV/PM EZOLV
Sets the number of times that the drive will try to restart.
V/f
OLV/PM
OLV/PM EZOLV
Sets the function that sends signals to the MFDO terminal set for Fault [H2-xx = E] while the drive
is automatically restarting.
Fault
Name
oL1
Motor Overload
Drive Overload
oL2
oL3
Overtorque Detection 1
Overtorque Detection 2
oL4
Overvoltage
ov
Input Phase Loss
PF
Motor Step-Out Detected
STPo
Uv1
DC Bus Undervoltage
Thermostat Fault
VLTS
Description
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Parameters to Disable Auto
Restart
L5-07
L5-07
L5-07
L5-07
L5-08
-
-
*1
L5-08
L5-53
Default
(Range)
0
(0 - 10 times)
Default
(Range)
0
(0, 1)
Figure 2.94