Note:
• The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
• This parameter sets the frequency reference of Multi-Step Speed 6.
d1-07: Reference 7
No.
Name
(Hex.)
d1-07
Reference 7
(0286)
RUN
Note:
• The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
• This parameter sets the frequency reference of Multi-Step Speed 7.
d1-08: Reference 8
No.
Name
(Hex.)
d1-08
Reference 8
(0287)
RUN
Note:
• The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
• This parameter sets the frequency reference of Multi-Step Speed 8.
d1-17: Jog Reference
No.
Name
(Hex.)
d1-17
Jog Reference
(0292)
RUN
Note:
The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values change.

d2: Reference Limits

d2 parameters set the upper and lower frequency limits to control the motor speed. Apply these parameters to for
example, run the motor at low-speed due to mechanical strength concerns, or if the motor should not be run at low
speed because of lubrication issues with the gears and bearings.
The upper frequency limit is set in d2-01 [Frequency Reference Upper Limit] and the lower limit is set in d2-02
[Frequency Reference Lower Limit].
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM EZOLV
OLV/PM
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
V/f
OLV/PM EZOLV
OLV/PM
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
V/f
OLV/PM EZOLV
OLV/PM
Sets the Jog frequency reference in the units from o1-03 [Frequency Display Unit Selection]. Set H1-
xx = 6 [MFDI Function Selection = Jog Reference Selection] to use the Jog frequency reference.
Figure 2.39 Upper and Lower Frequency Limits
Description
Description
Description
2.5 d: References
Default
(Range)
0.00 Hz
(0.00 - 400.00 Hz)
Default
(Range)
0.00 Hz
(0.00 - 400.00 Hz)
Default
(Range)
6.00 Hz
(0.00 - 400.00 Hz)