YASKAWA HV600 Manual page 516

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

3.3 LED Status Ring
LED
C
RUN
Flashing Quickly
*1
Refer to
Figure 3.6
for the difference between "flashing" and "flashing quickly".
516
Status
The drive is in regular operation.
Illuminated
• The drive is decelerating to stop.
*1
• The drive received a Run command with a frequency reference of 0 Hz.
Flashing
• The drive received a DC Injection Braking command.
• The drive received a Run command from the MFDI terminals when b1-02 = 0 [Run Command Selection 1 = Keypad] and
you changed the setting to b1-02 = 1 or 7 [Digital Input or AUTO Command + Term Run].
• The drive received a Run command from the MFDI terminals when the drive is not in Drive Mode.
• The drive received a Fast Stop command.
• The safety function shuts off the drive output.
*1
• The user pushed
• The drive is energized with an active Run command and b1-17 = 0 [Run Command at Power Up = Disregard Existing
RUN Command].
• The drive is set to coast-to-stop with timer (b1-03 = 3 [Stopping Method Selection = Coast to Stop with Timer]), and the
Run command is disabled then enabled during the Run wait time.
The motor is stopped.
OFF
Figure 3.6 LED Flashing Statuses
Figure 3.7 Relation between RUN LED and Drive Operation
Description
on the keypad when the drive is operated from a REMOTE source.
YASKAWA TOEPYAIHV6002A HV600 Drive Programming