b1-02: Run Command Selection 1
No.
Name
(Hex.)
b1-02
Run Command Selection 1
(0181)
0 : Keypad
The drive uses the keypad to enter the Run command.
Note:
The
on the keypad is on while keypad is the Run command source.
1 : Digital Input
The drive uses the control circuit terminals to enter the Run command. Select the input method for the Run command
with an H1-xx parameter.
Set H1-xx = 0, 40 to 43 [3-Wire Sequence, Run Command (2-Wire Sequence)]. The default setting is 2-wire sequence
1.
• 2-wire Sequence 1
This sequence has two input types: FWD/Stop and REV/Stop. Set A1-03 = 2220 [Initialize Parameters = 2-Wire
Initialization] to initialize the drive and set terminals S1 and S2 for a 2-wire sequence.
• 2-wire Sequence 2
This sequence has two input types: Run/Stop and FWD/REV.
• 3-Wire Sequence
This sequence has three input types: Run, Stop, and FWD/REV. Set A1-03 = 3330 [Initialize Parameters = 3-Wire
Initialization] to initialize the drive and set terminals S1, S2, and S5 for a 3-wire sequence.
2 : Serial Communications
The drive uses serial communications to enter the Run command.
3 : Option PCB
The drive uses a communications option card or input option card connected to the drive to enter the Run command.
Refer to the instruction manual included with the option card to install and set the option card.
Note:
If b1-02 = 3, but you did not connect an communications option card, oPE05 [Run Cmd/Freq Ref Source Sel Err] will flash on the keypad.
7 : AUTO Command + Term Run
The drive uses the AUTO Command to put the drive into AUTO Mode, and use the terminal set for Run [H1-xx = 40,
41, or 42] to enter the Run command.
8 : AUTO Command + Serial Run
The drive uses the AUTO Command to put the drive into AUTO Mode, and use the Serial Run command (register
0001) to enter the Run command.
9 : AUTO Command + Option Run
The drive uses the AUTO Command to put the drive into AUTO Mode, and use a communications or input option
connected to the drive to enter the Run command.
Note:
If you use these parameter settings at the same time, the drive will detect an oPE05 [Run Cmd/Freq Ref Source Sel Err]:
• S5-04 = 0 [HAND-OFF-AUTO Behavior = Legacy] and b1-02 = 0 to 3
• S5-10 = 2 [AUTO Key Memory at Power Down = AUTO Mode] and b1-02 = 0
b1-03: Stopping Method Selection
No.
Name
(Hex.)
b1-03
Stopping Method Selection
(0182)
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM EZOLV
OLV/PM
Sets the input method for the Run command.
V/f
OLV/PM EZOLV
OLV/PM
Sets the method to stop the motor after removing a Run command or entering a Stop command.
Description
Description
2.3 b: Application
Default
(Range)
7
(0 - 9)
2
Default
(Range)
1
(0 - 3)