Note:
Make sure that you also set jumper S5 on the control circuit terminal block when you change this parameter.
0 : 0 to 10 Vdc
2 : 4 to 20 mA
H4-08: Terminal AM Signal Level Select
No.
Name
(Hex.)
H4-08
Terminal AM Signal Level
Select
(0424)
Note:
Make sure that you also set jumper S5 on the control circuit terminal block when you change this parameter.
0 : 0 to 10 Vdc
2 : 4 to 20 mA
H4-20: Analog Power Monitor 100% Level
No.
Name
(Hex.)
H4-20
Analog Power Monitor
100% Level
(0B53)
Note:
• When H4-20 = 0.00 kW, the output power monitor 10 V level = motor rated power. The setting changes when the A1-02 [Control Method
Selection] value changes:
–A1-02 = 0 [V/f]: E2-11 [Motor Rated Power]
–A1-02 = 5 [OLV/PM]: E5-02 [PM Motor Rated Power]
–A1-02 = 8 [EZOLV]: E9-07 [Motor Rated Power]

H5: Memobus/Modbus Communication

H5 parameters configure the drive to use MEMOBUS/Modbus communications.
You can use the MEMOBUS/Modbus protocol over the RS-485 port (terminals D+ and D-) in the drive to use serial
communication with programmable controllers (PLC).
H5-01: Drive Node Address
No.
Name
(Hex.)
H5-01
Drive Node Address
(0425)
Note:
• Restart the drive after you change the parameter setting.
• Setting 0 will not let the drive respond to MEMOBUS/Modbus communications.
• When Y1-01 = 3 [Multiplex Mode = Memobus Network], the setting range changes when the Y9-25 [Highest Node Address] setting
changes.
To enable the drive to communicate with the controller (master) over MEMOBUS/Modbus communications, you
must set the drive with a slave address. Set H5-01 ≠ 0.
Set a slave address that is different from other slave devices.
H5-02: Communication Speed Selection
No.
Name
(Hex.)
H5-02
Communication Speed
Selection
(0426)
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM EZOLV
OLV/PM
Sets the MFAO terminal AM output signal level.
V/f
OLV/PM EZOLV
OLV/PM
Sets the level at 10 V when you set U1-08 [Output Power] for analog output.
V/f
OLV/PM EZOLV
OLV/PM
Sets the communication slave address for drives.
V/f
OLV/PM EZOLV
OLV/PM
Sets the communications speed for MEMOBUS/Modbus communications.
Description
Description
Description
Description
2.8 H: Terminal Functions
Default
(Range)
0
(0, 2)
Default
(Range)
0.00 kW
(0.00 - 650.00 kW)
Default
(Range)
1FH
(0 - FFH)
Default
(Range)
3
(0 - 8)
339
2