D6: Field Weakening; D7: Offset Frequency - YASKAWA HV600 Manual

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

Remove the Saved Frequency Reference Value
The procedure to remove the saved frequency reference value is different for different functions. Use these methods
to remove the value:
• Release the input programmed for Accel/Decel Ramp Hold [H1-xx = A].
• Set an Up or Down command while no Run command is active.
d4-10: Up/Down Freq Lower Limit Select
No.
Name
(Hex.)
d4-10
Up/Down Freq Lower Limit
Select
(02B6)
0 : Greater of d2-02 or Analog
The higher value between d2-02 [Frequency Reference Lower Limit] and an analog input programmed for Frequency
Reference [H3-02, H3-10 = 0] sets the lower frequency reference limit.
Note:
When you use External Reference 1/2 Selection [H1-xx = 2] to switch between the Up/Down function and an analog input as the reference
source, the analog value becomes the lower reference limit when the Up/Down command is active. Set d4-10 = 1 to isolate the Up/Down
function and the analog input value.
1 : d2-02
You can only use d2-02 to set the lower limit of the frequency reference.

d6: Field Weakening

d6 parameters set the field weakening function.
The field weakening function decreases the energy consumption of the motor. It decreases the output voltage of the
drive to a set level. The function decreases the motor excitation current inversely proportional to speed in a constant
output range, and does not let the induced voltage of the motor become more than the power supply voltage. To
enable this function, set Field Weakening [H1-xx = 63] ON.
Note:
Use the Field Weakening function in constant light-load applications. To control the energy consumption of the motor for other load
conditions, use the b8 parameters [Energy Saving].
d6-01: Field Weakening Level
No.
Name
(Hex.)
d6-01
Field Weakening Level
(02A0)
d6-02: Field Weakening Frequency Limit
No.
Name
(Hex.)
d6-02
Field Weakening Frequency
Limit
(02A1)
To enable the Field Weakening command, make sure that these two conditions are true:
• The output frequency ≥ d6-02.
• There is a speed agreement status.

d7: Offset Frequency

The drive will use 3 digital signal inputs, to add or subtract the set frequency (Offset frequency) to/from the frequency
reference and correct the speed. The drive uses the terminal set in H1-xx = 44 to 46 [MFDI Function Select = Add
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM EZOLV
OLV/PM
Sets the lower frequency limit for the Up/Down function.
V/f
OLV/PM EZOLV
OLV/PM
Sets the drive output voltage as a percentage of E1-05 [Maximum Output Voltage] when H1-xx = 63
[Field Weakening] is activated.
V/f
OLV/PM EZOLV
OLV/PM
Sets the minimum output frequency to start field weakening.
Description
Description
Description
2.5 d: References
Default
(Range)
0
(0, 1)
Default
(Range)
80%
(0 - 100%)
Default
(Range)
0.0 Hz
(0.0 - 400.0 Hz)
2
243