4.5 Control Circuit Wiring
Main Circuit Power Supply
ON
ON
OFF
Serial Communication Terminals
Refer to
Table 4.8
for a list of serial communication terminals and functions.
Type
Serial Communication

Control Circuit Terminal Configuration

The control circuit terminals are in the positions shown in
592
Table 4.7 Power Supply and Alarm Display
External 24 V Power Supply
ON
OFF
ON
Table 4.8 Serial Communication Terminals
Terminal
Terminal Name
Communication
• APOGEE FLN communications
D+
input/output (+)
• BACnet communications
• MEMOBUS/ Modbus communications
• Metasys N2 communications
Use an RS-485 cable to connect the drive.
Communication
D-
output (-)
AC
Signal ground
0 V
FE
Option card ground
o2-23
[External 24V Powerloss
[Alarm Display at Ext. 24V
Detection]
-
0 [Disabled]
1 [Enabled]
-
-
Note:
Set DIP switch S2 to ON to enable the
termination resistor in the last drive in an
APOGEE FLN, BACnet, MEMOBUS/ Modbus,
or Metasys N2 network.
Figure
4.23.
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
o2-26
Power]
-
-
-
L24v [Loss of External Power 24
Supply]
0 [Disabled]
"Ready" LED light flashes quickly
1 [Enabled]
EP24v [External Power 24V
Supply]
Function (Signal Level)
• RS-485
• APOGEE FLN communications: 4.8 kbps
• BACnet communications: Maximum 76.8 kbps
• MEMOBUS/Modbus communications:
Maximum 115.2 kbps
• Metasys N2 communications: 9.6 kbps
-