2.12 S: Special Applications
Sequence Timer 1 has no effect on the drive Run command. The drive starts correctly based on the status of the Run
command source set in b1-02 [Run Command Selection 1].
• When S2-04 = 1 or 2 [Run or Run - PID Disable] and the terminal set for H1-xx = 51 is not active:
The drive will run during the active time of Sequence Timer 1 when the drive has a Run command. The drive uses
the frequency reference set in S2-05 [Timer 1 Reference Source]. When S2-04 = 2, PID control is disabled.
If you activate the input from the terminal set for H1-xx = 52 [Sequence Timer Cancel] while Sequence Timer 1 is
active, the timer will be disabled until the next scheduled sequence timer occurrence. To enable Sequence Timer 1
again, disable and enable the drive Run command again. While Sequence Timer 1 is active, the terminal set for H2-xx
= 51 [MFDO Function Selection = Sequence Timer 1] will be active regardless of the S2-04 setting.
When S2-01 = S2-02, Sequence Timer 1 is active continuously for the days set in S2-03. The timer will start at the S2-
01/S2-02 time on the first day and stop at the same time on the last day. When you set only one day in S2-03, the
timer will stop at 11:59 on that day. When S2-03 = 1 [Daily], the timer will run from the start/stop time until 11:59
every day.
HOA Keypad will show these messages to identify the status of the drive and Sequence Timer 1:
• Sequence Timer 1 RUN: S2-04 = 1 or 2, Sequence Timer 1 is active and the drive is running.
• Sequence Timer OFF: The drive has a Run command, S2-04 = 1 or 2 and Sequence Timer 1 is not active.
When the drive is in Sequence Timer OFF condition, the drive should not detect Uv [DC Bus Undervoltage] or ov
[Overvoltage] fault, but only detect as an alarm.
Note:
If S2-03 > 0 and the HOA keypad is not connected, the drive will detect oPr [Keypad Connection Fault]. The o2-06 [Keypad Disconnect
Detection] setting does not have an effect.
Sequence Timers 2 to 4
These timers operate identically to Sequence Timer 1. Parameters S2-06 [Timer 2 Start Time] to S2-20 [Timer 4
Reference Source] set Sequence Timers 2 to 4.
Priority
When more than one sequence timers overlap, the timer with the lowest number has priority.
• Sequence Timer 1 = highest priority
• Sequence Timer 4 = lowest priority
Note:
Jog Forward/Reverse has higher priority than any of the Sequence Timers.
Figure 2.111
shows an example of sequence timer operation when you set the drive parameters as specified in
2.68.
Tine Display Format
o4-22 = 0
[24 Hour Clock]
432
Table 2.68 Parameter Settings for Example of Sequence Timer 1
Sequence Timer 1
S2-01 = 05:00
S2-02 = 15:00
S2-03 = 2
[Mon - Fri]
S2-04 = 1
[Run]
S2-05 = 0
[Operator (d1-01/YA-01)]
[Operator (d1-02/YA-02)]
Sequence Timer 2
Sequence Timer 3
S2-06 = 19:00
S2-07 = 22:00
S2-08 = 2
[Mon - Fri]
S2-09 = 2
[Run - PI Disable]
S2-10 = 1
[Operator (d1-03/YA-03)]
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Sequence Timer 4
S2-11 = 06:00
S2-16 = 17:00
S2-12 = 14:00
S2-17 = 21:00
S2-13 = 3
S2-18 = 10
[Sat - Sun]
S2-14 = 1
[Run]
[Digital Out Only]
S2-15 = 2
Table
[Sunday]
S2-19 = 0
-