YASKAWA HV600 Manual page 52

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

1.10 H: Terminal Functions
No.
Name
(Hex.)
H1-67
Terminal S7 On-Delay
Time
(39E7)
RUN
H1-71
Terminal S1 Off-Delay
Time
(39EB)
RUN
H1-72
Terminal S2 Off-Delay
Time
(39EC)
RUN
H1-73
Terminal S3 Off-Delay
Time
(39ED)
RUN
H1-74
Terminal S4 Off-Delay
Time
(39EE)
RUN
H1-75
Terminal S5 Off-Delay
Time
(39EF)
RUN
H1-76
Terminal S6 Off-Delay
Time
(39F0)
RUN
H1-77
Terminal S7 Off-Delay
Time
(39F1)
RUN
H1-xx: MFDI Setting Values
Setting Value
Function
0
3-Wire Sequence
3
Multi-Step Speed
Reference 1
4
Multi-Step Speed
Reference 2
5
Multi-Step Speed
Reference 3
6
Jog Reference Selection
7
Accel/Decel Time
Selection 1
8
Baseblock Command (N.
O.)
9
Baseblock Command (N.
C.)
A
Accel/Decel Ramp Hold
B
Overheat Alarm (oH2)
52
V/f
OLV/PM
OLV/PM EZOLV
Sets the length of time necessary for Terminal S7 to be closed before the drive does the
programmed function.
V/f
OLV/PM EZOLV
OLV/PM
Sets the length of time necessary for Terminal S1 to be open before the drive removes the
programmed function.
V/f
OLV/PM
OLV/PM EZOLV
Sets the length of time necessary for Terminal S2 to be open before the drive removes the
programmed function.
V/f
OLV/PM EZOLV
OLV/PM
Sets the length of time necessary for Terminal S3 to be open before the drive removes the
programmed function.
V/f
OLV/PM EZOLV
OLV/PM
Sets the length of time necessary for Terminal S4 to be open before the drive removes the
programmed function.
V/f
OLV/PM
OLV/PM EZOLV
Sets the length of time necessary for Terminal S5 to be open before the drive removes the
programmed function.
V/f
OLV/PM EZOLV
OLV/PM
Sets the length of time necessary for Terminal S6 to be open before the drive removes the
programmed function.
V/f
OLV/PM EZOLV
OLV/PM
Sets the length of time necessary for Terminal S7 to be open before the drive removes the
programmed function.
V/f
OLV/PM
OLV/PM EZOLV
Sets the direction of motor rotation for 3-wire sequence.
V/f
OLV/PM EZOLV
OLV/PM
Uses speed references d1-01 to d1-08 to set a multi-step speed reference.
V/f
OLV/PM EZOLV
OLV/PM
Uses speed references d1-01 to d1-08 to set a multi-step speed reference.
V/f
OLV/PM EZOLV
OLV/PM
Uses speed references d1-01 to d1-08 to set a multi-step speed reference.
V/f
OLV/PM
OLV/PM EZOLV
Sets the drive to use the JOG Frequency Reference (JOG command) set in d1-17 [Jog Reference]. The JOG Frequency
Reference (JOG command) overrides the d1-01 to d1-08 [References 1 to 8] settings.
V/f
OLV/PM EZOLV
OLV/PM
Sets the drive to use Acceleration/Deceleration Time 1 [C1-01, C1-02] or Acceleration/Deceleration Time 2 [C1-03,
C1-04].
V/f
OLV/PM EZOLV
OLV/PM
Sets the command that stops drive output and coasts the motor to stop when the input is ON.
ON : Baseblock (drive output stop)
OFF : Normal operation
V/f
OLV/PM
OLV/PM EZOLV
Sets the command that stops drive output and coasts the motor to stop when the input terminal is OFF.
ON : Normal operation
OFF : Baseblock (drive output stop)
V/f
OLV/PM EZOLV
OLV/PM
Momentarily pauses motor acceleration and deceleration when the terminal is turned ON, retains the output frequency
that was stored in the drive at the time of the pause, and restarts motor operation.
V/f
OLV/PM EZOLV
OLV/PM
Sets the drive to display an oH2 [Drive Overheat Warning] alarm when the input terminal is ON. The alarm does not
have an effect on drive operation.
Description
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Default
Ref.
(Range)
0.00 s
281
(0.00 - 300.00 s)
0.00 s
281
(0.00 - 300.00 s)
0.00 s
282
(0.00 - 300.00 s)
0.00 s
282
(0.00 - 300.00 s)
0.00 s
282
(0.00 - 300.00 s)
0.00 s
282
(0.00 - 300.00 s)
0.00 s
282
(0.00 - 300.00 s)
0.00 s
282
(0.00 - 300.00 s)
Ref.
282
283
283
284
284
284
284
284
285
285

Hide quick links: