C1-01:
C1-02:
C1-03:
Use Motor Selection to Switch Acceleration and Deceleration Times
When you set H1-xx = 16 [MFDI Function Selection = Motor 2 Selection], you can activate and deactivate the input
terminal to switch between motor 1 and motor 2.
Note:
You cannot use the Motor 2 Selection function with PM motors.
Table 2.32
shows the possible acceleration and deceleration time combinations when you use the Motor 2 Selection
function.
Table 2.32 Motor Selection and Acceleration and Deceleration Times
H1-xx = 7
[Accel/Decel Time Selection
1]
OFF
ON
*1
For software version PRG: 01011, when Motor 2 Selection is ON, the drive sets acceleration and deceleration times to 10.0 s.
C1-01: Acceleration Time 1
No.
Name
(Hex.)
C1-01
Acceleration Time 1
(0200)
RUN
C1-02: Deceleration Time 1
No.
Name
(Hex.)
C1-02
Deceleration Time 1
(0201)
RUN
C1-03: Acceleration Time 2
No.
Name
(Hex.)
C1-03
Acceleration Time 2
(0202)
RUN
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Figure 2.31 Timing Diagram of Acceleration and Deceleration Times
Motor 2 Selection: OFF
Acceleration Time
Deceleration Time
C1-01
C1-03
V/f
OLV/PM EZOLV
OLV/PM
Sets the length of time to accelerate from zero to maximum output frequency.
V/f
OLV/PM EZOLV
OLV/PM
Sets the length of time to decelerate from maximum output frequency to zero.
V/f
OLV/PM EZOLV
OLV/PM
Sets the length of time to accelerate from zero to maximum output frequency.
C1-04:
H1-xx = 7:
H1-xx = 16 [Motor 2 Selection]
Acceleration Time
C1-02
C1-05
C1-04
C1-07
Description
Description
Description
2.4 C: Tuning
Motor 2 Selection: ON
*1
Deceleration Time
C1-06
C1-08
Default
(Range)
30.0 s
(0.1 - 6000.0 s)
Default
(Range)
30.0 s
(0.1 - 6000.0 s)
Default
(Range)
30.0 s
(0.1 - 6000.0 s)