2.8 H: Terminal Functions
B: Torque Detection 1 (N.O.)
Setting Value
Function
B
Torque Detection 1 (N.O.)
ON : The output current/torque > L6-02 [Torque Detection Level 1], or the output current/torque < L6-
02 for longer than the time set in L6-03 [Torque Detection Time 1].
Note:
• When L6-01 ≥ 5, the drive will detect when the output current/torque is less than L6-02 for longer than L6-03.
• Refer to
L6: Torque Detection on page 375
C: Frequency Reference Loss
Setting Value
Function
C
Frequency Reference Loss
Note:
Refer to "L4-05: Fref Loss Detection Selection" for more information.
E: Fault
Setting Value
Function
E
Fault
Note:
The terminal will not activate for CPF00 and CPF01 [Control Circuit Error] faults.
F: Not Used
Setting Value
Function
F
Not Used
10: Alarm
Setting Value
Function
10
Alarm
11: Fault Reset Command Active
Setting Value
Function
11
Fault Reset Command
Active
12: Timer Output
Setting Value
Function
12
Timer Output
Note:
Refer to
Timer Function Operation on page 199
312
V/f
OLV/PM
OLV/PM EZOLV
The terminal activates when the drive detects overtorque or undertorque.
for more information.
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates when the drive detects a loss of frequency reference.
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates when the drive detects a fault.
V/f
OLV/PM
OLV/PM EZOLV
Use this setting for unused terminals or to use terminals in through mode. Also use this setting as the PLC contact output via
MEMOBUS/Modbus or the communication option. This signal does not function if you do not configure signals from the PLC.
V/f
OLV/PM
OLV/PM EZOLV
The terminal activates when the drive detects a minor fault.
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates when the drive receives the Reset command from the control circuit terminal, serial communications, or the
communication option.
V/f
OLV/PM EZOLV
OLV/PM
Use this setting when the drive uses the timer function as an output terminal.
for more information.
Description
Description
Description
Description
Description
Description
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming