2.12 S: Special Applications
Figure 2.113
shows an example of sequence timer operation when you set the drive parameters as specified in
2.70.
Tine Display Format
o4-22 = 0
[24 Hour Clock]
d1-01:
d1-02:
Sequence Timer Home Screen Text
When you set o1-40 = 0 [Home Screen Display Selection = Custom Monitor], the message text on the Status Monitor
will show the status of the Sequence Timer when the Sequence Timer has an effect on the drive Run condition.
• When you set the Sequence Timers to use for Digital Output only (S2-04 [Timer 1 Sequence Selection], S2-09
[Timer 2 Sequence Selection], S2-14 [Timer 3 Sequence Selection], and S2-19 [Timer 4 Reference Source] = 0
[Digital Out Only]), the message text will not show the status of the Sequence Timer.
• When the drive uses the Sequence Timers to overwrite the Run command in AUTO (S2-04, S2-09, S2-14, or S2-19
≠ 0), the drive will update the message text. Refer to
434
Table 2.70 Parameter Settings for Example of Sequence Timer 3
Sequence Timer 1
S2-01 = 05:00
S2-02 = 15:00
S2-03 = 2
[Mon - Fri]
S2-04 = 1
[Run]
S2-05 = 0
[Operator (d1-01/YA-01)]
[Operator (d1-02/YA-02)]
Figure 2.113 Example of Sequence Timer 3
Sequence Timer 2
Sequence Timer 3
S2-06 = 15:00
S2-07 = 22:00
S2-08 = 2
[Mon - Fri]
S2-09 = 2
[Run - PI Disable]
S2-10 = 1
[Operator (d1-03/YA-03)]
d1-03:
Table 2.71
for more information.
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Sequence Timer 4
S2-11 = 09:00
S2-12 = 24:00
S2-13 = 9
[Saturday]
[Timer Disabled]
S2-14 = 1
[Run]
S2-15 = 2
Table
-
-
S2-18 = 0
-
-