YASKAWA HV600 Manual page 444

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

2.12 S: Special Applications
S3-12: PI2 Control Disable Mode Sel
No.
Name
(Hex.)
S3-12
PI2 Control Disable Mode
Sel
(3225)
RUN
0 : No Output (0%)
U5-20 will show only 0.
1 : Lower Limit (S3-10)
U5-20 will show the lower limit of the PI2 Control Output set with S3-10 [PI2 Control Output Lower Limit].
2 : Setpoint
U5-20 will show the target setpoint of the PI2 Control that aligns with U5-18 [PI2 Control Feedback].
S3-13: PI2 Control Low Feedback Lvl
No.
Name
(Hex.)
S3-13
PI2 Control Low Feedback
Lvl
(3226)
RUN
Note:
Parameters S3-04 [PI2 Control Unit Selection], S3-03 [PI2 Control Decimal Place Pos], and S3-02 [PI2 Control Transducer Scale] set the
unit, resolution, and upper limit.
S3-14: PI2 Control Low Feedback Time
No.
Name
(Hex.)
S3-14
PI2 Control Low Feedback
Time
(3227)
RUN
S3-15: PI2 Control High Feedback Lvl
No.
Name
(Hex.)
S3-15
PI2 Control High Feedback
Lvl
(3228)
RUN
Note:
Parameters S3-04 [PI2 Control Unit Selection], S3-03 [PI2 Control Decimal Place Pos], and S3-02 [PI2 Control Transducer Scale] set the
unit, resolution, and upper limit.
S3-16: PI2 Control High Feedback Time
No.
Name
(Hex.)
S3-16
PI2 Control High Feedback
Time
(3229)
RUN
S3-17: PI2 Control Feedback Det Sel
No.
Name
(Hex.)
S3-17
PI2 Control Feedback Det
Sel
(322A)
RUN
444
V/f
OLV/PM
OLV/PM EZOLV
Sets what U5-20 [PI2 Control Output] will output when disabled.
V/f
OLV/PM
OLV/PM EZOLV
Sets the secondary PI low feedback detection level.
V/f
OLV/PM
OLV/PM EZOLV
Sets the secondary PI low feedback detection delay time in seconds.
V/f
OLV/PM EZOLV
OLV/PM
Sets the secondary PI high feedback detection level.
V/f
OLV/PM EZOLV
OLV/PM
Sets the secondary PI high feedback detection delay time in seconds.
V/f
OLV/PM EZOLV
OLV/PM
Sets when the low and high feedback detection multifunction outputs (71h and 72h) for PI2 Control
are active.
Description
Description
Description
Description
Description
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Default
(Range)
0
(0 - 2)
Default
(Range)
0.00
(0.00 - 600.00)
Default
(Range)
1.0 s
(0.0 - 25.5 s)
Default
(Range)
100.00
(0.00 - 600.00)
Default
(Range)
1.0 s
(0.0 - 25.5 s)
Default
(Range)
0
(0, 1)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents