n8-48: Pull-in/Light Load Id Current
No.
Name
(Hex.)
n8-48
Pull-in/Light Load Id
Current
(053B)
Adjust in the following situations.
• Slightly reduce this value if there is too much current when driving a light load at a constant speed.
• Increase the setting value in steps of 5% when hunting or vibration occurs during run at constant speed.
• Increase the setting value in steps of 5% if the motor stalls during run at constant speed.
n8-49: Heavy Load Id Current
No.
Name
(Hex.)
n8-49
Heavy Load Id Current
(053C)
When you use an IPM motor, you can use the reluctance torque of the motor to make the motor more efficient and
help conserve energy.
When you operate an SPN motor, set this parameter to 0.
Adjust this parameter in these conditions:
• If the load is large and motor rotation is not stable, decrease the setting value.
• If you change the E5 parameters [PM Motor Settings], set n8-49 = 0, then adjust this parameter.
n8-50: Medium Load Iq Level (High)
No.
Name
(Hex.)
n8-50
Medium Load Iq Level
(High)
(053D)
n8-51: Pull-in Current @ Acceleration
No.
Name
(Hex.)
n8-51
Pull-in Current @
Acceleration
(053E)
Adjust in the following situations.
• When the motor does not smoothly because of large loads, increase the setting value in 5% increments.
• If too much current flows during acceleration, decrease the setting value.
Note:
When A1-02 = 8 [Control Method Selection = EZOLV], this parameter will always be in effect for speed ranges less than n7-10 [Pull-in
Current Switching Speed].
n8-52: ACR P Gain
No.
Name
(Hex.)
n8-52
ACR P Gain
(053F)
Expert
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM EZOLV
OLV/PM
On the basis that parameter E5-03 [Motor Rated Current (FLA)] is the 100% value, this parameter
sets the d-axis current that flows to the motor during run at constant speed as a percentage.
V/f
OLV/PM
OLV/PM EZOLV
Sets the d-axis current to that the drive will supply to the motor to run it at a constant speed with a
heavy load. Considers E5-03 [PM Motor Rated Current (FLA)] to be 100%. Usually it is not
necessary to change this setting.
V/f
OLV/PM
OLV/PM EZOLV
Sets the load current level to start high efficiency control as a percentage of E5-03 [PM Motor Rated
Current (FLA)]. Usually it is not necessary to change this setting.
V/f
OLV/PM EZOLV
OLV/PM
Sets the pull-in current allowed to flow during acceleration/deceleration as a percentage of the motor
rated current.
V/f
OLV/PM EZOLV
OLV/PM
Sets the proportional gain of the current regulator. Usually it is not necessary to change this setting.
Description
Description
Description
Description
Description
2.10 n: Special Adjustment
Default
(Range)
30%
(0 - 200%)
Default
(Range)
Determined by E5-01
(-200.0 - +200.0%)
Default
(Range)
80%
(50 - 255%)
Default
(Range)
Determined by A1-02
(0 - 200%)
Default
(Range)
10.0
(-100.0 - 100.0)
2
399