YASKAWA HV600 Manual page 246

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

2.6 E: Motor Parameters
Note:
Be aware of the following points when manually setting V/f patterns.
• To set linear V/f characteristics at frequencies lower than E1-06 [Base Frequency], set E1-07 = E1-09 [Mid Point A Frequency = Minimum
Output Frequency]. In this application, the drive ignores E1-08 [Mid Point A Voltage].
• Set the five frequencies as specified by these rules: Incorrect settings will cause oPE10 [V/f Data Setting Error].
E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04 [Minimum Output Frequency ≤ Mid Point A Frequency < Base Frequency ≤ Mid Point B
Frequency ≤ Maximum Output Frequency]
• Setting E1-11 = 0 [Mid Point B Frequency = 0 Hz] disables E1-12 [Mid Point B Voltage]. Ensure that the four frequencies are set
according to the following rules;
E1-09 ≤ E1-07 < E1-06 ≤ E1-04
• When you use A1-03 [Initialize] to initialize the drive, it will not reset E1-03.
E1-01: Input AC Supply Voltage
No.
Name
(Hex.)
E1-01
Input AC Supply Voltage
(0300)
NOTICE: Set parameter E1-01 to align with the drive input voltage (not motor voltage). If this parameter is incorrect, the protective
functions of the drive will not operate correctly and it can cause damage to the drive.
Values Related to the Drive Input Voltage
The value set in E1-01 is the base value that the drive uses for the motor protective functions in
480 V class drive, the detection level changes for some motor protective functions.
Voltage
E1-01 Setting
208 V class
Setting value ≥ 400 V
480 V class
Setting value < 400 V
E1-03: V/f Pattern Selection
No.
Name
(Hex.)
E1-03
V/f Pattern Selection
(0302)
Note:
• Set the correct V/f pattern for the application and operation area. An incorrect V/f pattern can decrease motor torque and increase current
from overexcitation.
• Parameter A1-03 [Initialize Parameters] will not initialize the value of E1-03.
0 : Const Trq, 50Hz base, 50Hz max
246
Figure 2.43 V/f Pattern
V/f
OLV/PM EZOLV
OLV/PM
Sets the drive input voltage.
Table 2.39 Values Related to the Drive Input Voltage
ov Detection Level
All settings
410 V
820 V
820 V
V/f
OLV/PM EZOLV
OLV/PM
Sets the V/f pattern for the drive and motor. You can use one of the preset patterns or you can make a
custom pattern.
Description
Approximate Values
L2-05
[Undervoltage Detection
[KEB DC Bus Voltage
Lvl (Uv1)]
190 V
380 V
350 V
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Default
(Range)
208 V Class: 240 V,
480 V Class: 480 V
(208 V Class: 155 - 255 V,
480 V Class: 310 - 510 V)
Table
2.39. With a
L2-11
L3-17
[DC Bus Regulation
Setpoint]
Level]
260 V
375 V
500 V
750 V
460 V
750 V
Default
(Range)
F
(Determined by A1-02)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents