YASKAWA HV600 Manual page 298

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

2.8 H: Terminal Functions
The drive is in HAND Mode when AUTO Mode select input is not active.
OFF : OFF Mode or AUTO Mode
• S5-04 = 0:
The drive selects AUTO reference as specified by b1-01 [Frequency Reference Selection 1].
• S5-04 = 1:
The drive is in OFF or AUTO Mode.
70: Drive Enable 2
Setting Value
Function
70
Drive Enable 2
When you input the Run command before you turn ON the Drive Enable 2 terminal, it is not necessary to remove and
apply the Run command again. The drive will start to operate when the Run command and Drive Enable 2 are both
ON. If you turn OFF the terminal set for Drive Enable while the drive is operating, the drive will use the stopping
method set in b1-03 [Stopping Method Selection] to stop the motor.
ON : Run command is accepted.
OFF : Run command is disabled. When the drive is running, it stops according to b1-03 setting.
77: ASR Gain (C5-03) Select
Setting Value
Function
77
ASR Gain (C5-03) Select
ON : C5-03
Switches the proportional gain to C5-03 [ASR Proportional Gain 2].
OFF : C5-01
Switches the proportional gain to C5-01 [ASR Proportional Gain 1].
Note:
Refer to "C5: Automatic Speed Regulator (ASR)" for more information.
7A: KEB Ride-Thru 2 Activate (N.C.)
Setting Value
Function
7A
KEB Ride-Thru 2 Activate
(N.C.)
ON : Normal operation
OFF : Deceleration during momentary power loss
When KEB Ride-Thru 2 is input, the drive will use Single Drive KEB Ride-Thru 2 for KEB operation. The L2-29
[KEB Method Selection] setting will not have an effect.
Note:
• If you set KEB Ride-Thru 1 [H1-xx = 65, 66] and KEB Ride-Thru 2 [H1-xx = 7A, 7B] at the same time, the drive will detect oPE03 [Multi-
Function Input Setting Err].
• Refer to
KEB Ride-Thru Function on page 354
7B: KEB Ride-Thru 2 Activate (N.O.)
Setting Value
Function
7B
KEB Ride-Thru 2 Activate
(N.O.)
ON : Deceleration during momentary power loss
OFF : Normal operation
298
V/f
OLV/PM EZOLV
OLV/PM
Sets the function to show dnE [Drive Enabled] on the keypad and ignore Run commands when the terminal is OFF.
V/f
OLV/PM EZOLV
OLV/PM
Sets the function to switch the ASR proportional gain set in C5-01 [ASR Proportional Gain 1] and C5-03 [ASR Proportional Gain
2].
V/f
OLV/PM EZOLV
OLV/PM
Sets operation of the KEB2 function through the KEB Ride-Thru 2 (N.C.).
for more information.
V/f
OLV/PM EZOLV
OLV/PM
Sets operation of the KEB2 function through the KEB Ride-Thru 2 (N.O.).
Description
Description
Description
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents