N7: Ez Drive; N8: Pm Motor Control Tuning - YASKAWA HV600 Manual

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

n7: EZ Drive

No.
Name
(Hex.)
n7-01
Damping Gain for Low
Frequency
(3111)
Expert
n7-05
Response Gain for Load
Changes
(3115)
Expert
n7-07
Speed Calculation Gain1
(3117)
Expert
n7-08
Speed Calculation Gain2
(3118)
Expert
n7-10
Pull-in Current Switching
Speed
(311A)
Expert
n7-11
Pull-in Current Switch
Hysteresis Band
(311B)
Expert
n7-13
Pull-in Current Switching
Time
(311D)
Expert
n7-17
Resistance
TemperatureCorrection
(3122)

n8: PM Motor Control Tuning

No.
Name
(Hex.)
n8-23
ACR q Gain @PoleEst
(0556)
Expert
n8-24
ACR q Integral Time
@PoleEst
(0557)
Expert
n8-25
ACR q Limit @PoleEst
(0558)
Expert
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Description
V/f
OLV/PM EZOLV
OLV/PM
Sets the oscillation suppression gain for the low speed range.
V/f
OLV/PM
OLV/PM EZOLV
Sets the response gain related to changes in the load.
V/f
OLV/PM EZOLV
OLV/PM
Sets the speed calculation gain during usual operation. Usually it is not necessary to
change this setting.
V/f
OLV/PM EZOLV
OLV/PM
Sets the speed calculation gain during a speed search.
Note:
When E9-01 = 1 [Motor Type Selection = Permanent Magnet (PM)], the default
setting is 0 Hz and the setting range is 1.0 - 80.0 Hz.
V/f
OLV/PM
OLV/PM EZOLV
Parameter n8-51 [Pull-in Current @ Acceleration], is in effect when the output frequency
is ≤ n7-10, where the speed is set as a percentage of rated speed.
Note:
• The value set in n8-51 [Pull-in Current @ Acceleration] is enabled for speeds that
are not higher than n7-10 during deceleration. The value set in b8-01 [Energy Saving
Control Selection] is enabled for speeds higher than n7-10.
• If there is a large quantity of oscillation when you operate in the low speed range,
increase the setting value.
• When it is most important to save energy in the low speed range, decrease the setting
value.
V/f
OLV/PM EZOLV
OLV/PM
Sets the hysteresis level for Switching Speed set in n7-10 [Pull-in Current Switching
Speed]. When the speed is lower than n7-10 + n7-11 during acceleration, the drive enables
pull-in current.
Note:
• The value set in n8-51 [Pull-in Current @ Acceleration] is enabled for speeds that
are not higher than n7-10 + n7-11 during acceleration. The value set in b8-01 [Energy
Saving Control Selection] is enabled for speeds higher than n7-10 + n7-11.
• If there is a large quantity of oscillation when you operate in the low speed range,
increase the setting value.
• When it is most important to save energy in the low speed range, decrease the setting
value.
V/f
OLV/PM EZOLV
OLV/PM
Sets a time to enable the pull-in current commands.
If there is a large quantity of oscillation at speeds around n7-10 [Pull-in Current Switching
Speed], decrease the setting in decrements of 20 ms.
V/f
OLV/PM EZOLV
OLV/PM
Sets the function to adjust for changes in the motor resistance value caused by changes in
the temperature.
0 : Invalid
1 : Valid (Only 1 time)
2 : Valid (Every time)
Description
V/f
OLV/PM
OLV/PM EZOLV
Sets the proportional gain for current regulator q-axis control when the drive estimates the
initial pole. Usually it is not necessary to change this setting.
V/f
OLV/PM EZOLV
OLV/PM
Sets the integral time for current regulator q-axis control when the drive estimates the
initial pole. Usually it is not necessary to change this setting.
V/f
OLV/PM EZOLV
OLV/PM
Sets the q-axis limit of the current regulator when the drive estimates the initial pole.
Usually it is not necessary to change this setting.
1.12 n: Special Adjustment
Default
Ref.
(Range)
1.0
394
(0.1 - 10.0)
50
394
(10 - 1000)
15.0 Hz
394
(1.0 - 50.0 Hz)
25.0 Hz
395
(1.0 - 50.0 Hz)
10.0%
395
(0.0 - 100.0%)
5.0%
395
(1.0 - 20.0%)
100 ms
395
(0 - 1000 ms)
1
395
(0 to 2)
Default
Ref.
(Range)
0
396
(0 - 2000)
0.0 ms
396
(0.0 - 100.0 ms)
0%
396
(0 - 150%)
1
87