2.9 L: Protection Functions
Set one of these parameters to enable L3-20:
• L2-29 = 1 [KEB Method Selection = Single Drive KEB Ride-Thru 2]
• L3-04 = 2 [Decel Stall Prevention Selection = Automatic Decel Reduction]
• L3-11 = 1 [OV Suppression Function Select = Enabled]
• H1-xx = 7A or 7B [MFDI Function Select = KEB Ride-Thru 2 (N.O./N.C.)]
Note:
• If stall prevention during deceleration function causes ov [Overvoltage] and Uv1 [DC Bus Undervoltage] faults when you start deceleration
and L2-29 = 1, H1-xx = 7A or 7B, or L3-04 = 2, gradually increase this parameter in 0.1-unit increments. If the setting value is too high, it
can cause large speed or current ripples.
• If sudden increases in the regenerative load cause ov faults and L3-11 = 1, gradually increase this parameter in 0.1-unit increments. If the
setting value is too high, it can cause large speed or current ripples.
L3-21: OVSuppression Accel/Decel P Gain
No.
Name
(Hex.)
L3-21
OVSuppression Accel/Decel
P Gain
(0466)
Expert
Set one of these parameters to enable L3-21:
• L2-29 = 1 [Kinetic Energy Backup Method = Single Drive KEB Ride-Thru 2]
• L3-04 = 2 [Stall Prevention during Decel = Intelligent (Ignore Decel Ramp)]
• L3-11 = 1 [Overvoltage Suppression Select = Enabled]
• H1-xx = 7A or 7B [MFDI Function Selection = KEB Ride-Thru 2 Activate (N.O./N.C.)]
Note:
• If stall prevention during deceleration function causes large speed or current ripples and L2-29 = 1, H1-xx = 7A or 7B, or L3-04 = 2,
gradually decrease this parameter in 0.05-unit increments. If the drive detects ov [Overvoltage] or oC [Overcurrent], decrease this
parameter. If you decrease the gain too much, it can cause a delay in control in the DC bus voltage or the deceleration time could be longer
than the best deceleration time.
• If sudden increases in the regenerative load cause ov faults and L3-11 = 1, gradually increase this parameter in 0.1-unit increments. If there
are large speed ripples, gradually decrease this parameter in 0.05-unit increments.
L3-22: PM Stall Prevention Decel Time
No.
Name
(Hex.)
L3-22
PM Stall Prevention Decel
Time
(04F9)
Set this parameter to 0.0 s to disable this function. The drive will decelerates in the deceleration time applicable at the
time when a motor stall occurs.
L3-23: Stall P Reduction at Constant HP
No.
Name
(Hex.)
L3-23
Stall P Reduction at
Constant HP
(04FD)
0 : Use L3-06 for Entire Speed Range
The drive uses the level set in L3-06 [Stall Prevent Level during Run] through the full speed range.
1 : Automatic Reduction @ CHP Region
The drive decreases the Stall Prevention level during run in the constant power range. The lower limit is 40% of the
L3-06 value.
366
V/f
OLV/PM EZOLV
OLV/PM
Sets the proportional gain to calculate acceleration and deceleration rates.
V/f
OLV/PM EZOLV
OLV/PM
Sets the momentary deceleration time that the drive will use when it tries to accelerate a PM motor
and detected motor stalls. This function is applicable when L3-01 = 1 [Stall Prevent Select
duringAccel = General Purpose].
V/f
OLV/PM EZOLV
OLV/PM
Sets the function to automatically decrease the Stall Prevention Level during Run for constant output
ranges.
Description
Description
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Default
(Range)
1.00
(0.10 - 10.00)
Default
(Range)
0.0 s
(0.0 - 6000.0 s)
Default
(Range)
0
(0, 1)