YASKAWA HV600 Manual page 320

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

2.8 H: Terminal Functions
54: Sequence Timer 4
Setting Value
Function
54
Sequence Timer 4
58: UL6 Underload Detected
Setting Value
Function
58
UL6 Underload Detected
60: Internal Cooling Fan Failure
Setting Value
Function
60
Internal Cooling Fan Failure
61: Pole Position Detection Complete
Setting Value
Function
61
Pole Position Detection
Complete
62: Modbus Reg 1 Status Satisfied
Setting Value
Function
62
Modbus Reg 1 Status
Satisfied
63: Modbus Reg 2 Status Satisfied
Setting Value
Function
63
Modbus Reg 2 Status
Satisfied
69: External Power 24V Supply
Setting Value
Function
69
External Power 24V Supply
ON : An external 24V power supply supplies power.
OFF : An external 24V power supply does not supply power.
6A: Data Logger Error
Setting Value
Function
6A
Data Logger Error
71: Low PI2 Control Feedback Level
Setting Value
Function
71
Low PI2 Control Feedback
Level
320
V/f
OLV/PM
OLV/PM EZOLV
The terminal activates when Sequence Timer 4 is active.
V/f
OLV/PM
OLV/PM EZOLV
The terminal activates when the drive detected UL6 [Underload or Belt Break Detected].
V/f
OLV/PM
OLV/PM EZOLV
The terminal activates when the drive detects a cooling fan failure in the drive.
V/f
OLV/PM
OLV/PM EZOLV
The terminal activates when drive receives a Run command and the drive detects the motor magnetic pole position of the PM motor.
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates when the bit specified by H2-08 [Modbus Register 1 Bit Select] for the MEMOBUS register address set with
H2-07 [Modbus Register 1 Address Select] activates.
V/f
OLV/PM
OLV/PM EZOLV
The terminal activates when the bit specified by H2-10 [Modbus Register 2 Bit Select] for the MEMOBUS register address set with
H2-09 [Modbus Register 2 Address Select] activates.
V/f
OLV/PM
OLV/PM EZOLV
The terminal activates when there is an external 24V power supply between terminals PS-AC.
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates when the drive detects a LoG [Com Error / Abnormal SD card].
V/f
OLV/PM
OLV/PM EZOLV
The terminal activates when the PI2 Control Feedback Level is less than S3-13 [PI2 Control Low Feedback Lvl].
Description
Description
Description
Description
Description
Description
Description
Description
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents