YASKAWA HV600 Manual page 491

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

Note:
• The drive with the lowest Y9-21 value has the highest priority and will become the Lead Drive first. If more than one drive has the lowest
Y9-21 value, then Y9-01 [Lead Drive Selection] selects which drive becomes the lead.
• When you set Y9-21 to the same value for all drives on the MEMOBUS network, it will disable this function. If more than one drive has the
same Y9-21 value, then Y9-01 will select the next Lead Drive.
• To give First Drive (and Lead Drive) control back to the drive with highest priority level set in Y9-21, set Y9-24 [Lead Swap at Sleep Delay
Time] on the other drives with a lower priority level.
Y9-22: System Fault Retry Attempts
No.
Name
(Hex.)
Y9-22
System Fault Retry Attempts
(3E09)
RUN
Note:
Set this parameter to the same value for all drives on the network for correct operation.
Y9-23: Max Drives Allowed to Run
No.
Name
(Hex.)
Y9-23
Max Drives Allowed to Run
(3E0A)
Y9-24: Lead Swap at Sleep Delay Time
No.
Name
(Hex.)
Y9-24
Lead Swap at Sleep Delay
Time
(3E0B)
RUN
Note:
Set this parameter to 0 to disable the function.
Y9-25: Highest Node Address
No.
Name
(Hex.)
Y9-25
Highest Node Address
(3E0C)
Note:
For optimal network performance, set the serial communication address H5-01 [Drive Node Address] beginning with 01H consecutively up
to the last drive and then set this parameter to the final H5-01 address.
Y9-26: Master Time-out
No.
Name
(Hex.)
Y9-26
Master Time-out
(3E0D)
Y9-27: Network Recovery
No.
Name
(Hex.)
Y9-27
Network Recovery
(3E0E)
0 : Automatic
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM
OLV/PM EZOLV
Sets the number of times that the MEMOBUS Network will allow automatic restarts of system faults.
The drive uses L5-04 [Interval Method Restart Time] to select the time to try a system fault restart.
V/f
OLV/PM EZOLV
OLV/PM
Sets the maximum number of drives that can run on the system.
V/f
OLV/PM
OLV/PM EZOLV
Sets the length of time that the Lead Drive will be in Sleep Mode before the drive will request for a
swap when there is another drive available with a lower Y9-21 [Run Priority] setting.
V/f
OLV/PM
OLV/PM EZOLV
Sets the highest possible node address in the MEMOBUS network.
V/f
OLV/PM
OLV/PM EZOLV
Sets the minimum length of time that the slave drives will wait for a message from the master before
they do the action set in Y9-27 [Network Recovery].
V/f
OLV/PM EZOLV
OLV/PM
Sets the slave drive response when it does not receive a message from the master for the time set in
Y9-26 [Master Time-out].
2.14 Y: Application Features
Description
Description
Description
Description
Description
Description
Default
(Range)
5
(0 - 10)
Default
(Range)
4
(1 - 4)
Default
(Range)
0 s
(0 - 7200 s)
Default
(Range)
4
(2 - 4)
Default
(Range)
4.0 s
(1.0 - 10.0 s)
Default
2
(Range)
0
(0 - 3)
491