YASKAWA HV600 Manual page 437

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

Note:
• Default is when o4-22 = 1 [Time Format = 12 Hour Clock]. When o4-22 = 0 [24 Hour Clock], default is 00:00. When o4-22 = 2 [12 Hour
JP Clock], default is 00:00 AM.
• Range is when o4-22 = 1. When o4-22 = 0, range is 00:00 to 24:00. When o4-22 = 2, range is 00:00 AM to 11:59 PM.
S2-08: Timer 2 Day Selection
No.
Name
(Hex.)
S2-08
Timer 2 Day Selection
(320D)
0 : Timer disabled
1 : Daily
2 : Mon - Fri
3 : Sat - Sun
4 : Monday
5 : Tuesday
6 : Wednesday
7 : Thursday
8 : Friday
9 : Saturday
10 : Sunday
S2-09: Timer 2 Sequence Selection
No.
Name
(Hex.)
S2-09
Timer 2 Sequence Selection
(320E)
0 : Digital Out Only
1 : Run
2 : Run - PID Disable
3 : Allow Alternation
S2-10: Timer 2 Reference Source
No.
Name
(Hex.)
S2-10
Timer 2 Reference Source
(320F)
0 : Operator (d1-01/YA-01)
1 : Operator (d1-02/YA-02)
2 : Operator (d1-03/YA-03)
3 : Operator (d1-04/YA-04)
4 : Terminals
5 : Serial Com
6 : Option PCB
8 : Set by b1-01
Note:
For reference source 0 to 3, the drive will use d1-xx frequency reference when PID mode is disabled and YA-xx setpoint when PID is enabled.
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM EZOLV
OLV/PM
Sets the days for which sequence timer 2 is active.
V/f
OLV/PM EZOLV
OLV/PM
Sets the drive response when sequence timer 2 is active.
V/f
OLV/PM EZOLV
OLV/PM
Selects the frequency reference source to run the drive when sequence timer 2 is active (only
applicable when S2-09 > 0 [Timer 2 Sequence Selection ≠ 0]).
2.12 S: Special Applications
Description
Description
Description
Default
(Range)
0
(0 - 10)
Default
(Range)
0
(0 - 3)
Default
(Range)
0
(0 - 8)
2
437

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents