T4-01: EZ Tuning Mode Selection
No.
Name
(Hex.)
T4-01
EZ Tuning Mode Selection
(3130)
0 : Motor Parameter Setting
1 : Line-to-Line Resistance
T4-02: Motor Type Selection
No.
Name
(Hex.)
T4-02
Motor Type Selection
(3131)
0 : Induction (IM)
1 : Permanent Magnet (PM)
2 : Synchronous Reluctance (SynRM)
T4-03: Motor Max Revolutions
No.
Name
(Hex.)
T4-03
Motor Max Revolutions
(3132)
T4-04: Motor Rated Revolutions
No.
Name
(Hex.)
T4-04
Motor Rated Revolutions
(3133)
T4-05: Motor Rated Frequency
No.
Name
(Hex.)
T4-05
Motor Rated Frequency
(3134)
Note:
When T4-02 = 1, 2 [Motor Type Selection = PM, SynRM], input is not necessary because it assumes: Motor Rated Revolutions/60 × Number
of Motor Poles/2.
T4-06: Motor Rated Voltage
No.
Name
(Hex.)
T4-06
Motor Rated Voltage
(3135)
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM
OLV/PM EZOLV
Sets the type of Auto-Tuning for EZOLV control.
V/f
OLV/PM
OLV/PM EZOLV
Sets the type of motor.
V/f
OLV/PM
OLV/PM EZOLV
Sets the maximum motor revolutions (min
V/f
OLV/PM
OLV/PM EZOLV
-1
Sets rated rotation speed (min
) of the motor.
V/f
OLV/PM EZOLV
OLV/PM
Sets the rated frequency (Hz) of the motor.
V/f
OLV/PM EZOLV
OLV/PM
Sets the rated voltage (V) of the motor.
Description
Description
Description
-1
).
Description
Description
Description
2.13 T: Auto-Tuning
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0, 1, 2)
Default
(Range)
-
((40 to 120 Hz) × 60 × 2 /
E9-08)
Default
(Range)
-
((40 Hz to 120 Hz) × 60 × 2/
E9-08)
Default
(Range)
Determined by E9-01 and
o2-04
(40.0 - 120.0 Hz)
Default
(Range)
208 V Class: 230.0 V,
480 V Class: 460.0 V
(208 V Class: 0.0 - 255.0 V,
480 V Class: 0.0 - 510.0 V)