1.18 U: Monitors
No.
Name
(Hex.)
U2-11
Input Terminal Status @
Fault
(008A)
U2-12
Output Terminal Status @
Fault
(008B)
U2-13
Operation Status @ Fault
(008C)
U2-14
Elapsed Time @ Fault
(008D)
U2-15
SFS Output @ Fault
(07E0)
U2-16
q-Axis Current@Fault
(07E1)
U2-17
d-Axis Current@Fault
(07E2)
U2-20
Heatsink Temp @Fault
(008E)
116
V/f
OLV/PM EZOLV
OLV/PM
Shows the status of the MFDI terminals at the most recent fault where 1 = (ON) and 0 = (OFF).
For example, U2-11 shows "00000011" when terminals S1 and S2 are ON.
Use U1-10 [Input Terminal Status] to monitor the MFDI terminal status.
bit 0 : Terminal S1
bit 1 : Terminal S2
bit 2 : Terminal S3
bit 3 : Terminal S4
bit 4 : Terminal S5
bit 5 : Terminal S6
bit 6 : Terminal S7
bit 7 : Not used (normal value of 0).
V/f
OLV/PM EZOLV
OLV/PM
Shows the status of the MFDO terminals at the most recent fault where 1 = (ON) and 0 = (OFF).
For example, U2-12 shows "00000011" when terminals M1 and M3 are ON.
Use U1-11 [Output Terminal Status] to monitor the MFDO terminal status.
bit 0 : Terminals M1-M2
bit 1 : Terminals M3-M4
bit 2 : Terminals M5-M6
bit 3 : Not used (normal value of 0).
bit 4 : Not used (normal value of 0).
bit 5 : Not used (normal value of 0).
bit 6 : Not used (normal value of 0).
bit 7 : Fault relay MA/MB-MC
V/f
OLV/PM EZOLV
OLV/PM
Shows the status of the MFDO terminals at the most recent fault where 1 = (ON) and 0 = (OFF).
For example, U2-13 shows "00000001" during run.
Use U1-12 [Drive Status] to monitor the MFDO terminal status.
bit0 : During Run
bit1 : During zero-speed
bit2 : During reverse
bit3 : During fault reset signal input
bit4 : During speed agreement
bit5 : Drive ready
bit6 : During minor fault detection
bit7 : During fault detection
V/f
OLV/PM
OLV/PM EZOLV
Shows the cumulative operation time of the drive at the fault that occurred most recently.
Use U4-01 [Cumulative Ope Time] to monitor the cumulative operation time.
Unit: 1 h
V/f
OLV/PM EZOLV
OLV/PM
Shows the output frequency after soft start at the fault that occurred most recently.
Use U1-16 [SFS Output Frequency] to monitor the output frequency after soft start.
Unit: 0.01 Hz
V/f
OLV/PM
OLV/PM EZOLV
Shows the q-Axis current of the motor at the fault that occurred most recently.
Use U6-01 [Iq Secondary Current] to monitor the q-Axis current of the motor.
Unit: 0.1 %
V/f
OLV/PM
OLV/PM EZOLV
Shows the d-Axis current of the motor at the fault that occurred most recently.
Use U6-02 [Id ExcitationCurrent] to monitor the d-Axis current of the motor.
Unit: 0.1 %
V/f
OLV/PM EZOLV
OLV/PM
Shows the heatsink temperature at the fault that occurred most recently.
Use U4-08 [Heatsink Temperature] to monitor the temperature of the heatsink.
Unit: 1 °C
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
MFAO Signal Level
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available