YASKAWA HV600 Manual page 263

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

Note:
Set E9-01 = 0 [Motor Type Selection = Induction (IM)] before you set this parameter.
E9-10: Motor Line-to-Line Resistance
No.
Name
(Hex.)
E9-10
Motor Line-to-Line
Resistance
(11ED)
Note:
This value is the motor line-to-line resistance. Do not set this parameter with the per-phase resistance.
Stationary Auto-Tuning automatically sets this parameter. If you cannot do Stationary Auto-Tuning, use the test report
from the motor manufacturer. You can calculate the motor line-to-line resistance with one of these formulas:
• E-type insulation: the resistance value (Ω) shown on the test report at 75 °C × 0.92
• B-type insulation: the resistance value (Ω) shown on the test report at 75 °C × 0.92
• F-type insulation: the resistance value (Ω) shown on the test report at 115 °C × 0.87
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM EZOLV
OLV/PM
Sets the line-to-line resistance for the motor stator windings.
Description
2.6 E: Motor Parameters
Default
(Range)
Determined by o2-04
(0.000 - 65.000 Ω)
263
2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents