1.5 b: Application

1.5

b: Application

b1: Operation Mode Selection

No.
Name
(Hex.)
b1-01
Frequency Reference
Selection 1
(0180)
b1-02
Run Command Selection
1
(0181)
b1-03
Stopping Method
Selection
(0182)
b1-04
Reverse Operation
Selection
(0183)
b1-08
Run Command Select in
PRG Mode
(0187)
b1-11
Run Delay @ Stop
(01DF)
b1-12
Run Delay Memory
Selection
(01E0)
26
V/f
OLV/PM
OLV/PM EZOLV
Sets the input method for the frequency reference.
0 : Keypad
1 : Analog Input
2 : Serial Communications
3 : Option PCB
V/f
OLV/PM EZOLV
OLV/PM
Sets the input method for the Run command.
0 : Keypad
1 : Digital Input
2 : Serial Communications
3 : Option PCB
7 : AUTO Command + Term Run
8 : AUTO Command + Serial Run
9 : AUTO Command + Option Run
Note:
If you use these parameter settings at the same time, the drive will detect an oPE05
[Run Cmd/Freq Ref Source Sel Err]:
• S5-04 = 0 [HAND-OFF-AUTO Behavior = Legacy] and b1-02 = 0 to 3
• S5-10 = 2 [AUTO Key Memory at Power Down = AUTO Mode] and b1-02 = 0
V/f
OLV/PM EZOLV
OLV/PM
Sets the method to stop the motor after removing a Run command or entering a Stop
command.
Note:
When A1-02 = 5 or 8 [Control Method Selection = OLV/PM or EZOLV], the setting
range is 0, 1, 3.
0 : Ramp to Stop
1 : Coast to Stop
2 : DC Injection Braking to Stop
3 : Coast to Stop with Timer
V/f
OLV/PM EZOLV
OLV/PM
Sets the reverse operation function. Disable reverse operation in fan or pump applications
where reverse rotation is dangerous.
0 : Reverse Enabled
1 : Reverse Disabled
V/f
OLV/PM
OLV/PM EZOLV
Sets the conditions for the drive to accept a Run command entered from an external source
when using the keypad to set parameters.
0 : Disregard RUN while Programming
1 : Accept RUN while Programming
2 : Allow Programming Only at Stop
V/f
OLV/PM EZOLV
OLV/PM
Sets the amount of time that the drive will not accept the Run command again after the
Run command is lost.
Note:
• This parameter will operate for both AUTO Mode and HAND Mode.
• This parameter will operate when the drive goes to sleep then wakes up.
• The time set in this parameter does not apply for faults or Auto-Restarts.
• When there is an active Run command while the time set in b1-11 is active, the
keypad will show a [Start Delay] message as specified by the o1-82 [Message Screen
Display] display format.
V/f
OLV/PM EZOLV
OLV/PM
Sets how the drive saves the Run Delay Timer to the EEPROM during power loss.
0 : Disabled
1 : Only at Stop
2 : Running & Stop
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Default
Ref.
(Range)
1
177
(0 - 3)
7
179
(0 - 9)
1
179
(0 - 3)
1
182
(0, 1)
0
183
(0 - 2)
0.0 s
183
(0.0 - 6000.0 s)
2
184
(0 - 2)

Hide quick links: