2.3 b: Application
Note:
When you change b5-38 and b5-46, the drive will not automatically convert the parameters in
For example, when you set YA-01 = 70.0 [PSI] and change these parameters:
• b5-46 from 1 [PSI] to 8 [Bar]
• b5-38 from 145.0 to 10.0
The drive changes only the unit setting and YA-01 will be 70.0 [Bar]. When the setpoint value after you change b5-38 and b5-46 is more than
b5-38, the drive internally limits the setpoint value to 200% of b5-38. The drive regards the YA-01 setting as 20.0 [Bar].
Parameter Groups
b5
S5
Y1
Y2
Y4
Y9
YA
Monitor Groups
U1
U5
UA
Full-Scale of the PID Analog Input Signals
The full-scale of the analog signals listed in this table go from b5-71 [Min PID Transducer Scaling] to b5-38 [PID
User Unit Display Scaling].
H3-xx Setting
B
C
24
*1
Only when b5-01 = 1 [PID Mode Setting = Standard] and S5-03 = 1 [HAND Mode PID Selection = Enabled]
Note:
When you set b5-71 < 0, the drive appropriately scales the setpoint and feedback values of the drive, but internally limits to 0 when the
reported value from the transducer is negative.
206
Table 2.28 Parameters Set by b5-38 and b5-46
b5-71 [Min PID Transducer Scaling]
• S5-06 [HAND Setpoint]
• S5-12 [HAND Setpoint 2]
• Y1-04 [Sleep Wake-up Level]
• Y1-08 [Low Feedback Level]
• Y1-11 [High Feedback Level]
• Y1-14 [High Feedback Hysteresis Level]
• Y1-15 [Maximum Setpoint Difference]
• Y2-05 [Sleep Boost Level]
• Y2-08 [Delta Feedback Drop Level]
• Y2-25 [Anti-No-Flow Release Level]
• Y4-01 [Pre-Charge Level]
• Y4-18 [Differential Level]
• Y4-37 [Pressure Reached Hysteresis Lvl]
• Y9-10 [Staging Delta Feedback Level]
• Y9-14 [De-staging Delta Feedback Level]
• Y9-17 [Setpoint Modifier]
• Y9-34 [Low Feedback De-stage]
• YA-01 [Setpoint 1]
• YA-02 [Setpoint 2]
• YA-03 [Setpoint 3]
• YA-04 [Setpoint 4]
Table 2.29 Monitors Set by b5-38 and b5-46
• U1-60 [System Setpoint]
• U1-61 [System Feedback]
• U5-01 [PID Feedback]
• U5-04 [PID Setpoint]
• U5-79 [PI Feedback Backup]
• U5-81 [Differential PI Fdbk]
• U5-99 [PID Setpoint Command]
UA-01 [Network PID Feedback]
MFAI
PID Feedback
PID Setpoint
PID Feedback Backup
Table
2.28.
No.
No.
H3-xx Setting
2B
Emergency Override PID Feedback
2D
2E
HAND Frequency Ref or Setpoint
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
MFAI
Differential Level Source
*1