2.8 H: Terminal Functions
84: Dedicated Multi-Setpoint YA-03
Setting Value
Function
84
Dedicated Multi-Setpoint
YA-03
Note:
If you use this function and one of H1-xx = 3E or 3F [PID Setpoint Selection 1 or 2] at the same time, the drive will detect an oPE03 [Multi-
Function Input Setting Err].
ON : YA-03 is PID setpoint.
OFF : YA-01 [Setpoint 1], YA-02 [Setpoint 2], or YA-04 [Setpoint 4] is PID setpoint.
85: Dedicated Multi-Setpoint YA-04
Setting Value
Function
85
Dedicated Multi-Setpoint
YA-04
Note:
If you use this function and one of H1-xx = 3E or 3F [PID Setpoint Selection 1 or 2] at the same time, the drive will detect an oPE03 [Multi-
Function Input Setting Err].
ON : YA-04 is PID setpoint.
OFF : YA-01 [Setpoint 1], YA-02 [Setpoint 2], or YA-03 [Setpoint 3] is PID setpoint.
88: Thermostat Fault
Setting Value
Function
88
Thermostat Fault
Note:
This function is active when the drive is running.
If the drive is running in AUTO Mode or HAND Mode and if the terminal set for H1-xx = 88 [MFDI Function
Selection = Thermostat Fault] is ON or if the terminal set for H1-xx = 188 [!Thermostat Fault] is OFF, the drive will
detect VLTS.
90 to 96: DriveWorksEZ Digital Inputs 1 to 7
Setting Value
Function
90 - 96
DWEZ Digital Inputs 1 to 7
Note:
You cannot set values 90 to 96 for inverse output.
9F: DWEZ Disable
Setting Value
Function
9F
DWEZ Disable
Note:
Set A1-07 = 2 [DriveWorksEZ Function Selection = Digital input] to use this function.
ON : Disabled
OFF : Enabled
300
V/f
OLV/PM
OLV/PM EZOLV
Sets the function to set the PID setpoint to YA-03 [Setpoint 3]. Set this function and H1-xx = 83 [Dedicated Multi-Setpoint YA-02] at
the same time.
V/f
OLV/PM
OLV/PM EZOLV
Sets the function to set the PID setpoint to YA-04 [Setpoint 4]. Set this function, H1-xx = 83 [Dedicated Multi-Setpoint YA-02], and
H1-xx = 84 [Dedicated Multi-Setpoint YA-03] at the same time.
V/f
OLV/PM
OLV/PM EZOLV
Sets the drive to show the VLTS [Thermostat Fault] when the input terminal is ON.
V/f
OLV/PM EZOLV
OLV/PM
Set DriveWorksEZ digital inputs. Refer to the DriveWorksEZ online manual for more information.
V/f
OLV/PM
OLV/PM EZOLV
Sets operation of the DriveWorksEZ program saved in the drive.
Description
Description
Description
Description
Description