L: Protection Functions; L1: Motor Protection - YASKAWA HV600 Manual

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

2.9 L: Protection Functions

2.9

L: Protection Functions

L parameters set the following functions.
• Motor Overload Protection
• Operation During Momentary Power Loss
• Stall Prevention
• Speed Detection
• Auto Restart
• Detection of Overtorque/Undertorque
• Torque Limit
• Hardware Protection

L1: Motor Protection

L1 parameters set the motor overload protection function.
L1-01: Motor Overload (oL1) Protection
No.
Name
(Hex.)
L1-01
Motor Overload (oL1)
Protection
(0480)
This parameter enables and disables the motor overload protection with electronic thermal protectors.
The cooling capability of the motor changes when the speed control range of the motor changes. Use an electronic
thermal protector that aligns with the permitted load characteristics of the motor to select motor protection.
The electronic thermal protector of the drive uses these items to calculate motor overload tolerance and supply
overload protection for the motor:
• Output Current
• Output Frequency
• Motor thermal characteristics
• Time characteristics
If the drive detects motor overload, the drive will trigger an oL1 [Motor Overload] and stop the drive output.
Set H2-01 = 1F [Term M1-M2 Function Selection = Motor Overload Alarm (oL1)] to set a motor overload alarm. If
the motor overload level is more than 90% of the oL1 detection level, the output terminal turns ON and triggers an
overload alarm.
0 : Disabled
Disable motor protection when motor overload protection is not necessary or when the drive is operating more than
one motor.
Refer to
Figure 2.84
for an example of the circuit configuration to connect more than one motor to one drive.
Figure 2.84 Protection Circuit Configuration to Connect More than One Motor to One Drive
350
V/f
OLV/PM EZOLV
OLV/PM
Sets the motor overload protection with electronic thermal protectors.
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Default
(Range)
Determined by A1-02
(0 - 4)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents

Save PDF