1.10 H: Terminal Functions
Setting Value
Function
18
Torque Detection 2 (N.
O.)
19
Torque Detection 2 (N.C.)
1A
During Reverse
1B
During Baseblock (N.C.)
1C
Motor 2 Selection
1E
Executing Auto-Restart
1F
Motor Overload Alarm
(oL1)
20
Drive Overheat Pre-
Alarm (oH)
21
Safety Monitor Output
Status
2F
Maintenance Notification
30
During Torque Limit
37
During Frequency Output
38
Drive Enabled
39
Watt Hour Pulse Output
3A
Drive Overheat Alarm
3D
During Speed Search
42
Pressure Reached
4A
During KEB Ride-Thru
62
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates when the drive detects overtorque or undertorque.
ON : The output current/torque > L6-05 [Torque Detection Level 2], or the output current/torque < L6-05 for longer
than the time set in L6-06 [Torque Detection Time 2].
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the drive detects overtorque or undertorque.
OFF : The output current/torque > L6-05 [Torque Detection Level 2], or the output current/torque < L6-05 for longer
than the time set in L6-06 [Torque Detection Time 2].
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates when the motor operates in the reverse direction.
ON : The motor is operating in the reverse direction.
OFF : The motor is operating in the forward direction or the motor stopped.
V/f
OLV/PM EZOLV
OLV/PM
The terminal deactivates during baseblock. When the drive is in baseblock, the drive output transistor stops switching
and does not make DC bus voltage.
ON : The drive is not in baseblock.
OFF : During baseblock
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates when you select motor 2.
ON : Motor 2 Selection
OFF : Motor 1 Selection
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates when the Auto Restart function is trying to restart after a fault.
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates when the electronic thermal protection value of the motor overload protective function is a
minimum of 90% of the detection level.
V/f
OLV/PM
OLV/PM EZOLV
The terminal activates when the drive heatsink temperature is at the level set with L8-02 [Overheat Alarm Level].
V/f
OLV/PM
OLV/PM EZOLV
The terminal activates (safety stop state) when the safety circuit and safety diagnosis circuit are operating correctly and
when terminals H1-HC and H2-HC are OFF (Open).
ON : Safety stop state
OFF : Safety circuit fault or RUN/READY
V/f
OLV/PM
OLV/PM EZOLV
The terminal activates when drive components are at their estimated maintenance period.
Tells you about the maintenance period for these items:
• IGBT
• Cooling Fan
• Capacitor
• Soft charge bypass relay
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates when the torque reference is the torque limit set with L7 parameters, H3-02 or H3-10 [MFAI
Function Selection].
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates when the drive outputs frequency.
ON : The drive outputs frequency.
OFF : The drive does not output frequency.
V/f
OLV/PM EZOLV
OLV/PM
This terminal activates when the H1-xx = 6A [Drive Enable] terminal activates.
V/f
OLV/PM EZOLV
OLV/PM
Outputs the pulse that shows the watt hours.
V/f
OLV/PM
OLV/PM EZOLV
The terminal activates when the drive heatsink temperature is at the L8-02 [Overheat Alarm Level] setting while L8-03
= 4 [Overheat Pre-Alarm Selection = Operate at Reduced Speed (L8-19)] and the drive is running.
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates when the drive is doing speed search.
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates when the drive is at the Pressure Setpoint.
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates during KEB Ride-Thru.
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Ref.
315
315
316
316
316
316
316
317
317
317
317
317
318
318
318
318
318
319