Ya: Preset Setpoint; Yc: Foldback Features - YASKAWA HV600 Manual

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

No.
Name
(Hex.)
Y9-51
PI Aux Control Turn-Off
Method
(3E26)
Y9-98
Network Parameter Push
(3E55)

YA: Preset Setpoint

No.
Name
(Hex.)
YA-01
Setpoint 1
(3E58)
RUN
YA-02
Setpoint 2
(3E59)
RUN
YA-03
Setpoint 3
(3E5A)
RUN
YA-04
Setpoint 4
(3E5B)
RUN

YC: Foldback Features

No.
Name
(Hex.)
YC-01
Output Current Limit
Select
(3EBC)
YC-02
Current Limit
(3EBD)
RUN
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Description
V/f
OLV/PM EZOLV
OLV/PM
Sets the MEMOBUS Multiplex response to the PI Aux Control.
0 : Disabled
1 : Enabled
V/f
OLV/PM EZOLV
OLV/PM
Sets how the system sends System-wide parameters into the MEMOBUS Multiplex
network.
0 : Disabled
1 : Enabled/Prompt
Description
V/f
OLV/PM
OLV/PM EZOLV
Sets the PID Setpoint when b1-01 = 0 [Frequency Reference Selection 1 = Keypad or
Multi-Speed Selection].
Note:
Parameters b5-46 [PID Unit Display Selection], b5-38 [PID User Unit Display
Scaling], and b5-39 [PID User Unit Display Digits] set the unit, range, and resolution.
V/f
OLV/PM EZOLV
OLV/PM
Sets the PID Setpoint as specified by the Multi-Setpoint digital inputs.
Note:
Parameters b5-46 [PID Unit Display Selection], b5-38 [PID User Unit Display
Scaling], and b5-39 [PID User Unit Display Digits] set the unit, range, and resolution.
V/f
OLV/PM
OLV/PM EZOLV
Sets the PID Setpoint as specified by the Multi-Setpoint digital inputs.
Note:
Parameters b5-46 [PID Unit Display Selection], b5-38 [PID User Unit Display
Scaling], and b5-39 [PID User Unit Display Digits] set the unit, range, and resolution.
V/f
OLV/PM
OLV/PM EZOLV
Sets the PID Setpoint as specified by the Multi-Setpoint digital inputs.
Note:
Parameters b5-46 [PID Unit Display Selection], b5-38 [PID User Unit Display
Scaling], and b5-39 [PID User Unit Display Digits] set the unit, range, and resolution.
Description
V/f
OLV/PM EZOLV
OLV/PM
Sets the function to enable or disable the output current regulator.
0 : Disabled
1 : Enabled
V/f
OLV/PM EZOLV
OLV/PM
Sets the current limit.
Note:
Value is internally limited to 300% of the drive rated current set in n9-01 [Inverter
Rated Current].
1.19 Y: Application Features
Default
Ref.
(Range)
0
494
(0, 1)
1
494
(0, 1)
Default
Ref.
(Range)
0.00
496
(0.00 - 600.00)
0.00
496
(0.00 - 600.00)
0.00
496
(0.00 - 600.00)
0.00
496
(0.00 - 600.00)
Default
Ref.
(Range)
0
497
(0, 1)
0.0 A
497
(0.0 - 1000.0 A)
1
141