YASKAWA HV600 Manual page 279

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

H1-05: Terminal S5 Function Selection
No.
Name
(Hex.)
H1-05
Terminal S5 Function
Selection
(0402)
Note:
The default setting is 0 when the drive is initialized for 3-Wire Initialization [A1-03 = 3330].
H1-06: Terminal S6 Function Selection
No.
Name
(Hex.)
H1-06
Terminal S6 Function
Selection
(0403)
Note:
The default setting is 3 when the drive is initialized for 3-Wire Initialization [A1-03 = 3330].
H1-07: Terminal S7 Function Selection
No.
Name
(Hex.)
H1-07
Terminal S7 Function
Selection
(0404)
Note:
The default setting is 4 when the drive is initialized for 3-Wire Initialization [A1-03 = 3330].
MEMOBUS/Modbus MFDI 1 to MFDI 3 Function Selection
You can set the function for the MFDI to MEMOBUS register bit 0 to 2 of [15C0(Hex.)]. Use H1-40 to H1-42 [Mbus
Reg 15C0h bit0 to bit 2 Input Func] to select the function.
Note:
• Refer to H1-xx "MFDI setting values" for the setting values of the MFDI.
• You cannot set 0 [3-Wire Sequence] or 20 to 2F [External Fault] in H1-40 to H1-42.
• When you will not use H1-40 to H1-42, set them to F [Through Mode].
H1-40: Mbus Reg 15C0h bit0 Input Func
No.
Name
(Hex.)
H1-40
Mbus Reg 15C0h bit0 Input
Func
(0B54)
H1-41: Mbus Reg 15C0h bit1 Input Func
No.
Name
(Hex.)
H1-41
Mbus Reg 15C0h bit1 Input
Func
(0B55)
H1-42: Mbus Reg 15C0h bit2 Input Func
No.
Name
(Hex.)
H1-42
Mbus Reg 15C0h bit2 Input
Func
(0B56)
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM EZOLV
OLV/PM
Sets the function for MFDI terminal S5.
V/f
OLV/PM EZOLV
OLV/PM
Sets the function for MFDI terminal S6.
V/f
OLV/PM EZOLV
OLV/PM
Sets the function for MFDI terminal S7.
V/f
OLV/PM
OLV/PM EZOLV
Sets the MFDI function assigned to bit 0 of the MEMOBUS register 15C0 (Hex.).
V/f
OLV/PM
OLV/PM EZOLV
Sets the MFDI function assigned to bit 1 of the MEMOBUS register 15C0 (Hex.).
V/f
OLV/PM EZOLV
OLV/PM
Sets the MFDI function assigned to bit 2 of the MEMOBUS register 15C0 (Hex.).
Description
Description
Description
Description
Description
Description
2.8 H: Terminal Functions
Default
(Range)
3
(0 - 1FF)
Default
(Range)
4
(0 - 1FF)
Default
(Range)
6
(0 - 1FF)
Default
(Range)
F
(1 - 1FF)
Default
(Range)
F
(1 - 1FF)
Default
(Range)
F
(1 - 1FF)
279