H3: Analog Inputs - YASKAWA HV600 Manual

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

2.8 H: Terminal Functions
100 to 1C4: Inverse Outputs of 0 to C4
Setting Value
Function
100 to 1C4
Inverse Outputs of 0 to C4
For example, set H2-xx = 10E for the inverse output of E [Fault].

H3: Analog Inputs

WARNING! Sudden Movement Hazard. Do test runs and examine the drive to make sure that the command references are correct.
If you set the command reference incorrectly, it can cause damage to the drive or serious injury or death.
Drives have two analog input terminals, terminals A1 and A2. H3 parameters select the functions set to these analog
input terminals and adjust signal levels.
Table 2.55
shows the functions that you can set to analog input terminals. Use H3-02 and H3-10 [MFAI Function
Selection] to set functions.
Setting
Value
0
Frequency Reference
1
Frequency Gain
2
Auxiliary Frequency Reference 1
3
Auxiliary Frequency Reference 2
4
Output Voltage Bias
5
Accel/Decel Time Gain
6
DC Injection Braking Current
7
Torque Detection Level
8
Stall Prevent Level During Run
9
Output Frequency Lower Limit
B
PID Feedback
C
PID Setpoint
D
Frequency Bias
E
Motor Temperature (PTC Input)
F
Not Used
10
Forward Torque Limit
Note:
All analog input scaling uses gain and bias for adjustment. Set the gain and bias values correctly.
324
V/f
OLV/PM EZOLV
OLV/PM
Causes inverse output of the function for the selected MFDO. Uses the last two digits of 1xx to select which function to inversely
output.
Table 2.55 MFAI Setting Values
Function
Description
Setting
Ref.
Value
329
11
Reverse Torque Limit
330
12
Regenerative Torque Limit
330
15
General Torque Limit
330
16
Differential PID Feedback
330
1F
Not Used
330
24
PID Feedback Backup
331
25
PI2 Control Setpoint
331
26
PI2 Control Feedback
331
27
PI Auxiliary Control Feedback
332
2B
Emergency Override PID Feedback
332
2C
Emergency Override PID Setpoint
332
2D
Differential Level Source
332
2E
Hand Frequency Ref or Setpoint
332
30
DWEZ Analog Input 1
333
31
DWEZ Analog Input 2
333
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Function
Ref.
334
334
334
334
334
335
335
335
335
335
335
335
335
336
336