2.11 o: Keypad-Related Settings

2.11

o: Keypad-Related Settings

o parameters set keypad functions.

o1: Keypad Display Selection

o1 parameters select the parameters shown on the initial keypad screen and to configure the parameter setting units
and display units. These parameters also adjust the backlight and contrast of the LCD display.
Home Screen Display Format
o1-40 [Home Screen Display Selection] changes the display of the monitor shown on the Home screen. You can show
numerical values or one of these three displays on the Home screen monitor:
Bar Graph Display
A - Select Ux-xx [Monitors] with o1-24, o1-25, and o1-
26.
B - Configure display regions with o1-41, o1-43, and
o1-45.
Analog Gauge Display
A - Select Ux-xx [Monitors] with o1-24.
B - Configure display regions with o1-56.
Trend Plot Display
A - Select Ux-xx [Monitors] (Monitor 1) with o1-24.
B - Select Ux-xx [Monitors] (Monitor 2) with o1-25.
C - Set the maximum value of Monitor 2 with o1-50
D - Set the minimum value of Monitor 2 with o1-49
Full Screen Information Display
When you set o1-82 = 1 [Message Screen Display = ON], you can show an active status message in full screen on the
keypad.
404
C - Select display ranges with o1-42, o1-44, and o1-
46.
C - Select display ranges with o1-55.
E - Set the time scale with o1-51
F - Set the minimum value of Monitor 1 with o1-47
G - Set the maximum value of Monitor 1 with o1-48