2.8 H: Terminal Functions
■
5: Multi-Step Speed Reference 3
Setting Value
Function
5
Multi-Step Speed Reference
3
Note:
Refer to "Setting Procedures for Multi-step Speed Operation" in "d: Reference Settings" for more information.
■
6: Jog Reference Selection
Setting Value
Function
6
Jog Reference Selection
■
7: Accel/Decel Time Selection 1
Setting Value
Function
7
Accel/Decel Time Selection
1
Note:
Refer to
C1: Accel & Decel Time on page 222
■
8: Baseblock Command (N.O.)
Setting Value
Function
8
Baseblock Command (N.O.)
The keypad flashes bb [Baseblock]. If you cancel the baseblock command when the Run command is active, the drive
will restart the motor and use the speed search function.
ON : Baseblock (drive output stop)
OFF : Normal operation
■
9: Baseblock Command (N.C.)
Setting Value
Function
9
Baseblock Command (N.C.)
The keypad flashes bb [Baseblock]. If you cancel the baseblock command when the Run command is active, the drive
will restart the motor and use the speed search function.
ON : Normal operation
OFF : Baseblock (drive output stop)
284
V/f
OLV/PM
OLV/PM EZOLV
Uses speed references d1-01 to d1-08 to set a multi-step speed reference.
V/f
OLV/PM
OLV/PM EZOLV
Sets the drive to use the JOG Frequency Reference (JOG command) set in d1-17 [Jog Reference]. The JOG Frequency Reference
(JOG command) overrides the d1-01 to d1-08 [References 1 to 8] settings.
V/f
OLV/PM
OLV/PM EZOLV
Sets the drive to use Acceleration/Deceleration Time 1 [C1-01, C1-02] or Acceleration/Deceleration Time 2 [C1-03, C1-04].
for more information.
V/f
OLV/PM EZOLV
OLV/PM
Sets the command that stops drive output and coasts the motor to stop when the input is ON.
Figure 2.49 Baseblock Command Time Chart
V/f
OLV/PM EZOLV
OLV/PM
Sets the command that stops drive output and coasts the motor to stop when the input terminal is OFF.
Description
Description
Description
Description
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming