2.3 b: Application
b2-04:
Note:
If the drive detects oC [Overcurrent] when it uses DC Injection Braking to stop the motor, set L2-03 to a high value that will not trigger oC.
3 : Coast to Stop with Timer
When you enter the Stop command or turn OFF the Run command, the drive turns OFF the output and coasts the
motor to stop. The drive ignores the Run command until the "Run wait time t" is expired.
To start the drive again, enter the Run command after the "Run wait time t" is expired.
The active deceleration time and the output frequency when drive receives the Stop command determine the length of
"Run wait time t".
L2-03:
b1-04: Reverse Operation Selection
No.
Name
(Hex.)
b1-04
Reverse Operation Selection
(0183)
182
Figure 2.7 DC Injection Braking Time and Output Frequency
Figure 2.8 Coast to Stop with Timer
Figure 2.9 Run Wait Time and Output Frequency
V/f
OLV/PM EZOLV
OLV/PM
Sets the reverse operation function. Disable reverse operation in fan or pump applications where
reverse rotation is dangerous.
E1-04:
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Default
(Range)
1
(0, 1)