YASKAWA HV600 Manual page 109

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

No.
Name
(Hex.)
S6-13
EMOVR Option Fault
ON
(3244)
Expert
S6-14
EMOVR Application 1
Fault ON
(3245)
Expert
S6-16
EMOVR Customer
Safety Mode
(3247)
S6-17
EMOVR BAS Interlock
Mode
(3248)
S6-23
OV2 Detect Time
(324E)
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Description
V/f
OLV/PM
OLV/PM EZOLV
Sets the bit to enable fault detection during Emergency Override.
bit 0 : bUS - Option Communication
bit 1 : CE - Communication Error
bit 2 : E5 - SI-T3 Watch Dog Timer
bit 3 : EF0 - Option Card External Fault
bit 4 : PE1 - PLC Fault 1
bit 5 : PE2 - PLC Fault 2
bit 6 : nSE - Node Setup Error
bit 7 to 15 : Reserved
Note:
The drive sets the bits in Hex.
V/f
OLV/PM EZOLV
OLV/PM
Sets the bit to enable fault detection during Emergency Override.
bit 0 : EFx - External Faults
bit 1 : Reserved
bit 2 : HLCE - High Level Communications Error
bit 3 : bAT - HOA Keypad Battery Voltage Low
bit 4 : TiM - Keypad Time Not Set
bit 5 : bCE - Bluetooth Communication Fault
bit 6 : dWF2 - DriveWorksEZ Fault 2
bit 7 : dWF3 - DriveWorksEZ Fault 3
bit 8 : dWFL - DriveWorksEZ Fault
bit 9 : MSL - Net Master Lost
bit 10 : VLTS - Thermostat Fault
bit 11 to 15 : Reserved
Note:
The drive sets the bits in Hex.
V/f
OLV/PM EZOLV
OLV/PM
Sets the status for the customer safety input (when programmed) that must occur for
Emergency Override to function.
0 : Customer Safety Ignored
1 : EMOVRun Only When Safety OK
2 : EMOVRun Only When Safety NOT OK
Note:
You must set a customer safety to a Digital Input for this parameter to have an effect.
V/f
OLV/PM EZOLV
OLV/PM
Sets the status for the BAS Interlock input (when programmed) that must occur for
Emergency Override to function.
0 : BAS Interlock Ignored
1 : EMOVRun Only When Interlock OK
2 : EMOVRun When Interlock NOT OK
Note:
Parameter has no effect if BAS Interlock is not programmed to a Digital Input.
V/f
OLV/PM EZOLV
OLV/PM
Sets the detection time of ov2 [DC Bus Overvoltage 2] in 0.1 s increments.
Note:
Set this parameter to 0.0 s to disable ov2 detection.
1.16 S: Special Applications
Default
Ref.
(Range)
0
458
(0 - FFFF)
0
458
(0 - FFFF)
0
459
(0 - 2)
0
459
(0 - 2)
10.0 s
459
(0.0 - 1200.0 s)
1
109

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents