When terminal S1 (Run command) activates for 1 ms minimum, the drive rotates the motor. When terminal S2 (Stop
command) deactivates, the drive stops. When terminal Sx that is set in 3-wire sequence deactivates, the drive operates
in the forward direction, and when it activates, the drive operates in the reverse direction.
WARNING! Sudden Movement Hazard. Set the MFDI parameters before you close control circuit switches. Incorrect Run/Stop
circuit sequence settings can cause serious injury or death from moving equipment.
WARNING! Sudden Movement Hazard. When you use a 3-Wire sequence, set A1-03 = 3330 [Initialize Parameters = 3-Wire
Initialization] and make sure that b1-17 = 0 [Run Command at Power Up = Disregard Existing RUN Command] (default). If you do
not correctly set the drive parameters for 3-Wire operation before you energize the drive, the motor can suddenly rotate when you
energize the drive.
.
Note:
• To input the Run command, activate the terminal for 1 ms minimum.
• The default setting for b1-17 [Run Command at Power Up] is 0 [Disregard Existing RUN command]. If you enable the Run command
when the drive is energized, the protective function activates and the
1 [Accept Existing RUN Command].
3: Multi-Step Speed Reference 1
Setting Value
Function
3
Multi-Step Speed Reference
1
Note:
Refer to "Setting Procedures for Multi-step Speed Operation" in "d: Reference Settings" for more information.
4: Multi-Step Speed Reference 2
Setting Value
Function
4
Multi-Step Speed Reference
2
Note:
Refer to "Setting Procedures for Multi-step Speed Operation" in "d: Reference Settings" for more information.
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Figure 2.47 3-Wire Sequence Wiring Example
Figure 2.48 3-Wire Sequence Time Chart
V/f
OLV/PM EZOLV
OLV/PM
Uses speed references d1-01 to d1-08 to set a multi-step speed reference.
V/f
OLV/PM EZOLV
OLV/PM
Uses speed references d1-01 to d1-08 to set a multi-step speed reference.
2.8 H: Terminal Functions