H5: Serial Communication - YASKAWA HV600 Manual

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

No.
Name
(Hex.)
H4-03
Terminal FM Analog
Output Bias
(041F)
RUN
H4-04
Terminal AM Analog
Output Select
(0420)
H4-05
Terminal AM Analog
Output Gain
(0421)
RUN
H4-06
Terminal AM Analog
Output Bias
(0422)
RUN
H4-07
Terminal FM Signal
Level Select
(0423)
H4-08
Terminal AM Signal
Level Select
(0424)
H4-20
Analog Power Monitor
100% Level
(0B53)

H5: Serial Communication

No.
Name
(Hex.)
H5-01
Drive Node Address
(0425)
H5-02
Communication Speed
Selection
(0426)
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Description
V/f
OLV/PM
OLV/PM EZOLV
Sets the bias of the monitor signal that is sent from MFAO terminal FM.
Set the level of the analog signal sent from terminal FM at 10 V or 20 mA as 100% when
an output for monitoring items is 0%.
V/f
OLV/PM EZOLV
OLV/PM
Sets the monitoring number to be output from the MFAO terminal AM.
Set the x-xx part of the Ux-xx [Monitor]. For example, set H4-04 = 103 to monitor U1-03
[Output Current].
V/f
OLV/PM
OLV/PM EZOLV
Sets the gain of the monitor signal that is sent from MFAO terminal AM.
When an output for monitoring items is 0%, this parameter sets the analog signal output
level from the AM terminal at 10 V or 20 mA as 100%.
V/f
OLV/PM
OLV/PM EZOLV
Sets the bias of the monitor signal that is sent from MFAO terminal AM.
When an output for monitoring items is 0%, this parameter sets the analog signal output
level from the AM terminal at 10 V or 20 mA as 0%.
V/f
OLV/PM
OLV/PM EZOLV
Sets the MFAO terminal FM output signal level.
Note:
Set jumper S5 on the control circuit terminal block accordingly when you change this
parameter.
0 : 0 to 10 Vdc
2 : 4 to 20 mA
V/f
OLV/PM EZOLV
OLV/PM
Sets the MFAO terminal AM output signal level.
Note:
Set jumper S5 on the control circuit terminal block accordingly when you change this
parameter.
0 : 0 to 10 Vdc
2 : 4 to 20 mA
V/f
OLV/PM
OLV/PM EZOLV
Sets the level at 10 V when you set U1-08 [Output Power] for analog output.
Description
V/f
OLV/PM
OLV/PM EZOLV
Sets the communication slave address for drives.
Note:
• Restart the drive after you change the parameter setting.
• Setting 0 will not let the drive respond to MEMOBUS/Modbus communications.
• When Y1-01 = 3 [Multiplex Mode = Memobus Network], the setting range changes
when the Y9-25 [Highest Node Address] setting changes.
V/f
OLV/PM
OLV/PM EZOLV
Sets the communications speed for MEMOBUS/Modbus communications.
Note:
Re-energize the drive or set H5-20 = 1 [Communication Parameters Reload = Reload
Now] after you change the parameter setting.
0 : 1200 bps
1 : 2400 bps
2 : 4800 bps
3 : 9600 bps
4 : 19.2 kbps
5 : 38.4 kbps
6 : 57.6 kbps
7 : 76.8 kbps
8 : 115.2 kbps
1.10 H: Terminal Functions
Default
Ref.
(Range)
0.0%
338
(-999.9 - +999.9%)
103
338
(000 - 999)
50.0%
338
(-999.9 - +999.9%)
0.0%
338
(-999.9 - +999.9%)
0
338
(0, 2)
0
339
(0, 2)
0.00 kW
339
(0.00 - 650.00 kW)
Default
Ref.
(Range)
1FH
339
(0 - FFH)
3
339
(0 - 8)
1
73