YASKAWA HV600 Manual page 478

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

2.14 Y: Application Features
Y4-19: Differential Lvl Detection Time
No.
Name
(Hex.)
Y4-19
Differential Lvl Detection
Time
(3D0C)
RUN
Y4-20: Differential Level Detection Sel
No.
Name
(Hex.)
Y4-20
Differential Level Detection
Sel
(3D0D)
RUN
0 : Fault (and Digital Out)
1 : Alarm (and Digital Out)
2 : Digital Out Only
Y4-22: Low City On-Delay Time
No.
Name
(Hex.)
Y4-22
Low City On-Delay Time
(3D0F)
RUN
Y4-23: Low City Off-Delay Time
No.
Name
(Hex.)
Y4-23
Low City Off-Delay Time
(3D10)
RUN
Y4-24: Low City Alarm Text
No.
Name
(Hex.)
Y4-24
Low City Alarm Text
(3D11)
RUN
0 : Low City Pressure
1 : Low Suction Pressure
2 : Low Water in Tank
Y4-36: Pressure Reached Exit Conditions
No.
Name
(Hex.)
Y4-36
Pressure Reached Exit
Conditions
(3D1D)
RUN
0 : Hysteresis Above & Below
The terminal set for H2-xx = 42 [MFDO Function Selection = Pressure Reached] will deactivate when the Feedback
is less than the "Setpoint - Hysteresis" or more than the "Setpoint + Hysteresis" for the time set in Y4-39 [Pressure
Reached Off Delay Time].
1 : Hysteresis 1-Way
478
V/f
OLV/PM EZOLV
OLV/PM
Sets the length of time that the difference between PID Feedback and the Differential Feedback must
be more than Y4-18 [Differential Level] before the drive will respond as specified by Y4-20
[Differential Level Detection Selection].
V/f
OLV/PM EZOLV
OLV/PM
Sets the drive response during a Differential Level Detected condition.
V/f
OLV/PM EZOLV
OLV/PM
Sets the length of time that the drive will wait to stop when the drive detects a Low City Pressure
condition.
V/f
OLV/PM
OLV/PM EZOLV
Sets the length of time that the drive will wait to start again after you clear a Low City Pressure
condition.
V/f
OLV/PM EZOLV
OLV/PM
Sets the alarm message to show on the keypad when the drive detects a Low City Pressure condition.
V/f
OLV/PM EZOLV
OLV/PM
Sets how the digital output responds to Feedback changes after it activates.
Description
Description
Description
Description
Description
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Default
(Range)
10 s
(0 - 3600 s)
Default
(Range)
0
(0 - 2)
Default
(Range)
10 s
(1 - 1000 s)
Default
(Range)
5 s
(0 - 1000 s)
Default
(Range)
0
(0 - 2)
Default
(Range)
1
(0, 1)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents

Save PDF